Problem
Possible Cause
Action
Unit cools when heat 
is called for
Incorrect wiring
Refer to applicable wiring diagram
Defective solenoid coil
Check for continuity of coil
Reversing valve fails to shift
Block condenser coil & switch unit to cooling. Allow 
pressure to build up in system, then switch to 
heating. If valve fails to shift, replace valve.
Inoperative system switch
Check for continuity of system switch
Problem
Possible Cause
Action
Cooling adequate, 
but heating 
insuffi cient
Heating capillary tube partially restricted
Check for partially starved outer coil. Replace 
heating capillary tube
Check valve leaking internally
Switch unit several times from heating to cooling. 
Check temperature rise across coil. Refer to 
specifi cation sheet for correct temperature rise
Reversing valve failing to shift completely; 
bypassing hot gas
De-energize solenoid coil, raise head pressure, 
energize solenoid to break loose. If valve fails to 
make complete shift, replace valve.
Heat / Cool Room Air Conditioners: Troubleshooting Tips