NOTICE:
   
The method of venting the gas pressure switch has been changed 
 
The American National Standard Institute updated their standard (ANSI Z21.10.1) to address 
the issue of accidental or unintended ignition of flammable vapors.  This standard update forced 
the water heater manufacturers to make changes to there water heaters.  
 
Changes with the design of water heaters have necessitated a change in the installation 
requirement of a bleed tube on the gas pressure switch used in our water heater control kits.  
The change in the ANSI standard has forced the redesign of the air intake to the burners on the 
water heaters, resulting in the sealing of the access panel of the burner chamber.  This sealing 
of the access panel into the burner chamber area eliminates the ability to route a bleed tube 
from the vent side of the gas pressure switch into the burner chamber.   
 
To eliminate the need of installing the bleed tube, orifices are installed into the gas pressure 
switch inlet and vent ports.  These orifices are used to restrict the flow of gas through the 
pressure switch in the event of a rupture of the switch diaphragm.  This method is regularly used 
on most gas pressure regulators.  With the removal of the bleed tube, a screened cover has 
been added to the vent port of the gas pressure switch to eliminate foreign material from getting 
into the vent port. 
 
 
NEW 
OLD 
Form #46457600 10/03