TROUBLESHOOTING
Continued 
OBSERvED PROBLEM
ODS/pilot  lights  but  flame 
goes  out  when  control  knob 
is released
Burner  does  not  light  after 
ODS/pilot is lit
Delayed ignition of burner
Burner backfiring during com-
bustion
Burner  plaque(s)  does  not 
glow
Slight  smoke  or  odor  during 
initial operation
Heater  produces  a  clicking/
ticking noise just after burner 
is lit or shut off
REMEDY
1. Press in control knob fully
2. After ODS/pilot lights, keep 
control knob pressed in 30 
seconds
3. Fully open equipment shut-
off valve
4. A) Contact local natural or 
propane/LP gas company 
  B)  Clean  ODS/pilot  (see 
Cleaning and Maintenance
page 18) or replace ODS/
pilot assembly 
5. Hand  tighten  until  snug, 
then tighten 1/4 turn more
6. Replace pilot assembly
7. Replace control valve
1. Clean burner (see Cleaning 
and Maintenance, page 18) 
or replace burner orifice
2. Contact  local  natural  or 
propane/LP gas company
1. Contact  local  natural  or 
propane/LP gas company
2. Clean burner (see Cleaning 
and Maintenance, page 18) 
or replace burner orifice
1. Clean burner (see Cleaning 
and Maintenance, page 18) 
or replace burner orifice
2. Replace damaged burner
3. Replace gas regulator
1. Replace burner
2. Contact local natural or pro-
pane/LP gas company
3.  Turn  control  knob  until  it 
locks at desired setting
1. Problem will stop after a few 
hours of operation
1. This is normal with most heat-
ers. If noise is excessive, con-
tact qualified service person
POSSIBLE CAUSE
1. Control  knob  not  fully 
pressed in
2. Control knob not pressed in 
long enough
3. Equipment shutoff valve not 
fully open
4. Pilot  flame  not  touching 
thermocouple,  which  al-
lows thermocouple to cool, 
causing  pilot  flame  to  go 
out. This problem could be 
caused  by  one  or  both  of 
the following:
  A) Low gas pressure
  B) Dirty or partially clogged 
ODS/pilot 
5. Thermocouple  connection 
loose at control valve 
6. Thermocouple damaged
7. Control valve damaged
1. Burner orifice clogged
2. Inlet  gas  pressure  is  too 
low
1. Manifold  pressure  is  too 
low
2. Burner orifice clogged
1. Burner orifice is clogged or 
damaged
2. Damaged burner
3. Gas regulator defective
1. Plaque damaged
2. Inlet  gas  pressure  is  too 
low
3. Control  knob  set  between 
locked positions
1. Residues from manufactur-
ing processes
1. Metal  expanding  while 
heating or contracting while 
cooling