The 
SG Modular
Series utilize Replaceable Protection Modules.
SENSOR CABLE INTERFACE
TO FRONT PANEL DISPLAY
PHASE BUS
KEYED (GROUNDED)
MOUNTING BRACKET
YELLOW LED
NEUTRAL TO GROUND WARNING INDICATOR
NORMAL OPERATION = OFF
(NOT PRESENT ON DELTA CONFIGURATIONS)
[Figure #12:  Module Ø Side End Cap]
THERE ARE NO USER SERVICEABLE PARTS INSIDE MAIN HOUSING
SG160K, SG240K and SG320K  Models:
The specific product you have in service may be configured for any one of the following voltages:
 AC Service(s)
120 or 240Vac, Single Phase
120/240Vac, Split Phase
240 or 480Vac, Three Phase Delta
120/240Vac, Three Phase Delta (High Leg)
120/208Vac, 3 Phase Wye
NEUTRAL
BUS
Phase
"A"
RPM
GROUND
BUS
DRY CONTACT INTERFACE
NO
C
NC
 277/480Vac, Three Phase,
4 Wire + Ground
 AC Service:
LOCATION OF
OPTIONAL
SURGE COUNTER
A
C
SURGE
RATING
160kA (  )
240kA (  )
320kA (  )
Phase
"C"
RPM
SURGE
RATING
160kA (  )
240kA (  )
320kA (  )
Phase
"B"
RPM
SURGE
RATING
160kA (  )
240kA (  )
320kA (  )
B
SENSOR
CABLE
[Figure #11:  Internal Layout]
INTERNAL LAYOUT
1. Make Sure the power has been turned off to the SG unit.
Never work on the SPD unit while energized.
2. Disconnect the Sensor Cable from the module. 
(Ø Side End Cap)
3. Remove the 1/4 20 bolts securing the module to the 
phase and neutral tabs. One bolt at each end of the 
module. The compression lug comes off also. 
4. Remove the  2 #6 Screws (1 at each end of the unit) 
securing the module to the Back Plane PC Board.
5. Remove the module from the SG unit.
6. To mount the replacement module reverse steps 4, 3 
and 2.  Do not forget to reinstall the compression lug. 
7. Close the SG cabinet door and reconnect power.
MMOODDUULLEE RREEMMOOVVAALL && RREEPPLLAACCEEMMEENNTT
GREEN LED’s
PROTECTION MODE STATUS
(NORMAL OPERATION = ON)
277/480Vac, 3 Phase Wye
220/380Vac, 3 Phase Wye
230/400Vac, 3 Phase Wye
240/415Vac, 3 Phase Wye
MODULE
MODULE
MODULE