The appliance is merely one component of a larger system. The other 
equally important component is the venting system. This is necessary for 
achieving the required flow of combustion air to the fire chamber and for 
safely removing unwanted combustion by-products from the appliance.  
If the venting system’s design does not promote these ends, the system 
may not function properly. Poorly functioning venting systems may create 
performance problems as well as be a safety hazard.  A draft test should 
This manual describes the installation and operation of the Canyon™ C310 
non-catalytic wood heaters. These heaters meet the U.S. Environmental 
Protection Agency’s emissions limits for wood heaters sold on or after 
July 1, 1990. This heater has been developed, tested and constructed 
in accordance with the requirements of UL 1482, ULC S628 and HUD 
standards and is listed by OMNI Test Laboratories, Portland, OR. It has 
been approved for residential and alcove installations.
Your  wood  fireplace  insert  is  dependent  upon  a  properly  functioning 
chimney for optimum performance. It is a high efficiency appliance that 
loses much less heat up the chimney than older appliances and fireplaces. 
For this reason it is important to match the fireplace insert to the chimney. 
The chimney has two functions:  
1. It draws combustion air into the appliance (without air, no fuel will 
burn) and 
2. It exhausts combustion by-products. Your new Country™ Collection 
fireplace insert is what is known as a “natural draft” appliance. 
The appliance depends solely on the natural draft of the chimney system 
to draw combustion air into the unit. Draft is the force that moves air from 
the appliance up into the chimney. The amount of draft in your chimney 
depends on the length of the chimney, local geography, nearby obstructions 
and other factors. Too much draft may cause excessive temperatures in the 
appliance (overfiring). Slow or inadequate draft equals poor combustion 
and possible smoking problems. The following are some conditions that 
may contribute to poor chimney draft:  
1. A chimney too large for your appliance. 
2. A chimney with not enough height to produce adequate draft.
3. A chimney with excessive height (this may allow exhaust to cool too 
much before exiting, which will stall the rate the exhaust exits). 
4. Offsets in the venting system are too restrictive (see Chimney Guide-
lines).
Inadequate draft will cause the appliance to leak smoke into the room 
through the fireplace insert and the chimney connector joints. 
Excessive draft may cause an uncontrollable burn or a glowing red fire-
place insert or chimney part. 
Overfiring Damage - If the heater or chimney connector glows, you are 
overfiring. Other symptoms may include: Cracking, warping or burning 
out of components, plated doors may turn color, stove glass may develop 
a haze, which will not come off with cleaning.
Overfiring of a fireplace insert is a condition where excessive temperatures 
are reached, beyond the design capabilities of the appliance. The dam-
age that occurs from overfiring is not covered under the manufacturer’s 
limited warranty.
Also see Troubleshooting on Page 16.
TESTING INFORMATION
DRAFT REqUIREMENTS
SELECTING THE PROPER VENTING SYSTEM
(MJ) Add chimney height requirements (done 8-10-09)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
read greater than .0’ W.C. (inches water column) and less than .08” 
W.C.  As per NFPA-211 standard (see paragraph below), the installer 
must take into account all variables within the installation and install the 
appliance in such a manner that satisfies the draft requirements of the 
appliance.  See Chimney Guidelines below to assist you in selecting the 
proper venting system for your installation.
American National Standards Institute ANSI/NFPA 11, Standard for 
Chimneys,  Fireplaces,  Vents,  and  Solid  Fuel-Burning  Appliances 
- See Draft Section:  A chimney or vent shall be so designed and con-
structed to develop a flow sufficient to completely remove all flue and 
vent gases to the outside atmosphere. The venting system shall satisfy 
the draft requirements of the connected appliance in accordance with the 
manufacturer’s instructions.
Chimney Guidelines:
•  This appliance requires approximately 12 feet minimum of “effective 
draw” provided by the venting system.  As a rule of thumb, every 90 
degree total direction change in the venting will result in a loss of 
approximately 5 feet of “effective draw.”  Example: If two 45 degree 
offsets are used, subtract 5 feet from the actual vertical vent height 
to determine your “effective draw.”  In this case if you had 14 feet of 
vertical vent, the effective draw would only be approximately 9 feet 
(14 ft. - 5 ft. = 9 ft.), therefore it may be necessary to add additional 
height to the venting system.
•  If the venting system is all vertical and the total vent length above the 
flue outlet exceeds 14 feet, it is recommended that the 8” to 6” pipe 
reducer is used (cat. no. 71134) and a 6” venting system be installed.  
At higher elevations, this may not be necessary.
•  In well insulated and weather tight homes, it may be difficult to establish 
a good draft up your chimney. The poor draft is caused by a shortage 
of air in the house (see Negative Pressure Warning on Page 5).
Chimney Height Requirements
The chimney must extend 3’ (.92m) above the level of roof penetration 
and a minimum of 2’ (.61m) higher than any roof surface within 10’ 
(3m) (see below).  Check with your local building officials for additional 
requirements for your area.
To pass inspection in nearly any jurisdiction, the chimney must meet both 
safety and exhaust flow requirements. The (3’ by) 2’ by 10’ rule applies 
to both masonry and factory-built chimneys.
* Ref. USA - National Standard, NFPA 211-latest edition and Canada
National Standard CSA B365-01-latest edition. Vents installed with a
listed cap shall terminate in accordance with the terms of the cap’s
listings.
Figure 1
- Chimney Height Requirements
Less than
10' (3 m)
10'
(3 m)
3' (914 mm)
Min.
2’ (610 mm)  Min.
(914 mm)
Min.
3'