lift-master hazardous nema 79 用户手册

下载
页码 24
6
TO AVOID SERIOUS PERSONAL INJURY OR DEATH
FROM ELECTROCUTION, DISCONNECT ELECTRIC
POWER BEFORE MANUALLY MOVING LIMIT NUTS.
WARNING
CAUTION
WARNING
WARNING
LIMIT SWITCH ADJUSTMENT
MAKE SURE THE LIMIT NUTS ARE POSITIONED BETWEEN THE LIMIT SWITCH ACTUATORS BEFORE
PROCEEDING WITH ADJUSTMENTS.
If other problems persist, call our toll-free number for
assistance - 1-800-528-2806.
1.  To adjust limit nuts depress retaining plate to allow
nut to spin freely.  After adjustment, release plate
and ensure it seats fully in slots of both nuts.
2.  To  increase door travel, spin nut away  from
actuator. To decrease door travel, spin limit nut
toward actuator.  
3.  Adjust open limit nut so that door will stop in open
position with the bottom of the door even with top
of door opening.
4.  Repeat Steps 1 and 2 for close cycle. Adjust close
limit nut so that actuator is engaged as door fully
seats at the floor.
Retaining Plate
CLOSE Limit Switch
SAFETY
(Aux. Close) Limit Switch
OPEN Limit Switch
Actuator
Aux. OPEN Limit Switch
SENSING EDGES
All types of sensing edges with an isolated normally
open (N.O.) output are compatible with your operator.
This includes pneumatic and electric edges.  If your
door does not have a bottom sensing edge and you
wish to purchase one, contact the supplier of your
operator.
If not pre-installed by the door manufacturer, mount
the sensing edge on the door according to the
instructions provided with the edge.  The sensing
edge may be electrically connected by either coiled
cord or take-up reel. Refer to the steps below.
Important Notes:
a) Proceed with Limit Switch Adjustments before
making any sensing edge wiring connections to
operator as described below.
b) Electrician must hardwire the junction box to the
operator electrical box in accordance with local
codes.
ENTRAPMENT PROTECTION ACCESSORIES (OPTIONAL)
IT IS STRONGLY RECOMMENDED THAT A
SENSING EDGE OR OTHER ENTRAPMENT
PROTECTION DEVICE BE USED IN
CONJUNCTION WITH THIS OPERATOR.
WIRING:
For wiring of your sensing device to the operator,
refer to the wiring diagram supplied with your
operator.  See field connection terminals identified
as Sensing Device or Safety Edge.
TAKE-UP REEL: Take-up reel should be installed
12" above the top of the door.
COIL CORD:  Connect operator end of coil cord to
junction box (not supplied) fastened to the wall
approximately halfway up the door opening.