<scaling> 
Indicates which type of scaling is applied to the alias item. 
The parameters that follow this value depend on the type 
used. Possible scaling types are 0 (none), 1 (linear), 2 
(square root), 3 (gain/offset), and 4 (expression). 
<high raw>, 
<low raw>, 
<high scaled>, 
<low scaled>, 
<clamp> 
Linear or square-root scaling parameters include the raw 
high and low values, scaled high and low values, and a 
clamping option. Possible clamp types are 0 (none), 1 
(clamp low value), 2 (clamp high value), and 3 (clamp both 
high and low values). 
<gain>, 
<offset> 
Gain/offset scaling parameters include a scaling factor and 
an offset. 
"Input Expression","Output 
Expression" 
Expression scaling parameters include input and output 
expressions. The input expression is applied to the value 
from the OPC item when reading. The output expression is 
applied to values going to the OPC item when writing. 
These equations should be reciprocals of each other.