Robust DataComm rdc485fos-dv-2p-st Converter 规格指南

下载
页码 1
Making Industrial Data Flow Like Water ... Safely, Silently, & Sanely
Robust DataComm Pte Ltd (USA) 26471 Portola Pkwy #1E-242, Foothill Ranch CA 92610-1743, +1,972-248-7466 (International) 
18 Kaki Bukit Road 3 #02-08 Entrepreneur Business Centre Singapore 415978, +65,6487-5624
The rdc485fos safely and easily connects your 
panel mounted RS-422/485 devices to fiber optic 
cables up to 11 km long, providing the ultimate in 
isolation, surge, and noise protection.  Even the 
RS-422/485 port is galvanically isolated from the 
DC supply ground.  ST connector, plus the quality 
Hewlett Packard components used are 
guaranteed to work with 9/125 µm fiber sizes.
Isolation, industrial design, small size, DIN rail 
mount, user indication, and wide range DC 
supply make the rdc485fos a very engineer- 
friendly device for your industrial data 
communication system.
Model: rdc485fos
RS-422/485 to Fiber Optics Converter 
(Single Mode)
Dimensions in mm (and inches)
25 (1.0)
79 (3.1)
85.5 (
3
.4)
90.5 (
3
.6)
93.0 (
3
.7)
EN 50 022 - 7.5mm
EN 50 035
EN 50 022 - 15mm
98 (3.9)
Specification
Signal Type
Voltage Level
Permitted Surge
Power Supply to 
Fiber/RS-485
Order Information
rdc485fos
-
-
-
5v
5v +/- 5% Regulated DC Supply
9 to 36v Unregulated DC Supply
Power Supply Configuration
dv
hv
38 to 58v Unregulated DC Supply
non-isolated, RS-485 SGnd = supply V-
2.5Kv isolation between RS-485 & supply
1p
Galvanic Isolation Configuration
2p
Boxes in bold denote factory default options
Connector Configuration
ST bayonet connector (® of AT&T)
st
-
Galvanic Isolation Configuration
c
d
5-way Screw Connector
9 Pin D-shell Connector
9 to 36 vDC
5v DC +/- 5%
38 to 58 vDC
User Indications
Max Speed
Character Setting
User Indications
Practical Distance
: at least 115Kbps at standard distances
: transparent, no configuration required
: Txd and Rxd have LED (yellow) indications
: less than 3000m for RS-485, 13 km for fiber
  (requires quality, low-cap cable < 50 pf/m)
: EIA/RS-422A & RS-485A
: -7 to +12vDC
: +/- 25 vDC
: -40C to +65C
: -40C to +100C
: 10 to 90% RH, non-condensing
: wire up to 2.5mm (12 AWG)
: nylon polymide, fungus and termite resistant
  self-extinguishing
: approx 130g
: DIN EN 50 022 or DIN EN 50 035
Mechanical / Environment
Communication
Power Supply
Isolation
(Version 1.0) Specifications subject to change without notice.
Block Diagram
Isolated
Supply
T+
R+
Gnd2
T-
5-pin Removable Compression Terminal Block
V+
V--
Fl
o
at
in
g RS
-485 Po
rt
ST I
n
te
rface
LED
R-
Main
Supply
LED
LED
T+
T-
Gnd2
screw terminals
screw terminals
LED
TX
RX
Copyright © 2003 RDC
RS-485 (compatible with EIA-422)
Connector
Fiber Size
Insertion Loss
Technology
Link Loss Budget
Fiber Optic
: ST (bayonet) 
: 9/125 µm single mode fiber
: 0.2 dB typically
: 1310 nm wavelength, ELED
: typically 9 dBm
: 1-port = none ; 2-port = 2.5Kv
Operating Range
Storage Range
Relative Humidity
Terminals
Case Material
Weight
Mounting Rail
: 50 mA (Nominal) @ 24 vDC
: 240 mA (Norminal)
: 25 mA (Norminal) @ 48 vDC
: Green LED for each isolated supply
www.robustdc.com