Puls QS10.241 Power Supply 规格指南
QS10.241, QS10.241-A1/ -C1/ -D1
Q-Series
24V,
10A,
S
INGLE
P
HASE
I
NPUT
13. F
RONT
S
IDE AND
U
SER
E
LEMENTS
Fig. 13-1 Front side
A Input
Terminals (Quick-connect spring-clamp terminals)
N,
L
Line input
PE (Protective Earth) input
B Output
Terminals (Quick-connect spring-clamp terminals, two pins per
pole)
+ Positive output
+ Positive output
– Negative (return) output
C DC-OK
Relay
Contact
(Quick-connect spring-clamp terminals)
The DC-OK relay contact is synchronized with the DC-OK LED.
See chapter 8 for details.
See chapter 8 for details.
D Output voltage potentiometer
Open the flap to adjust the output voltage. Factory set: 24.1V
E DC-OK
LED
(green)
On, when the output voltage is >90% of the adjusted output voltage
F Overload
LED
(red)
On, when the voltage on the output terminals is <90% of the adjusted
output voltage, or in case of a short circuit in the output. Input voltage is
required
Flashing, when the unit has switched off due to over-temperature.
output voltage, or in case of a short circuit in the output. Input voltage is
required
Flashing, when the unit has switched off due to over-temperature.
Indicators, LEDs
Overload LED
DC-OK LED
DC-OK Contact
Normal mode
OFF
ON
Closed
During BonusPower
®
OFF
ON
Closed
Overload (V
OUT
< 90%)
ON
OFF
Open
Output short circuit
ON
OFF
Open
Temperature Shut-down
Intermitted
OFF
Open
No input power
OFF
OFF
Open
Nov. 2011 / Rev. 2.1 DS-QS10.241-EN
All parameters are specified at 24V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
All parameters are specified at 24V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.