ZTE Corporation ZXG-OB06 用户手册

下载
页码 117
 
ZXG10 OB06 ZTE  Integrated Outdoor GSM Base Station Technical Manual 
18 
Confidential and Proprietary Information of ZTE CORPORATION 
Power subrack 
Batteries (4): 75 kg 
Bearing capacity of a single concrete platform: >800 kg 
Power Supply 
Power Supply Range of Power Supply 
System 
Input voltage: 88 VAC~300 VAC, optional. 
Power Consumption Indexes 
The maximal power consumption of each module is as follows: 
TRM (×6): 200 W per TRM 
CMM (2 pieces): 15 W per CMM;  
AEM (×6): 15 W per AEM 
Internal mixed-flow fan (×3): 40 W per fan 
Internal axial flow fan (×3): 20 W per fan 
Fan for HEX: 60 W 
Transmission: 100 W 
Battery charging: 1500 W 
Heater: 2500 W 
Maintenance socket: 500 W 
When fully configured, the power consumption of the whole system is < 
6511W. 
Ambient Conditions 
Requirements for Grounding and Lightning 
Protection 
OB06 outdoor BTS features a lightning-protection capability of B+C level.