S610S Manual  - Hardware Installer Manual  - Version 1.8 
47 
will be Relay 0.  The readers then provide up to four additional spare relays, one and two on the 
master, numbers three and four on the exit. 
Ensure all related relay cabling requirements have been met.  A GP or general purpose input can be 
configured to trigger a relay switch, which can be wired to a sounder or a light for example. 
 
Mapping an input signal to a relay switch.   
Ensure 
Local output disabled
 is unchecked. 
Connecting a Sounder.  
If a S600S reader is part of an interlock system, the second relay on the Master reader may be used 
to emit an interlock signal.  A sounder can be connected to relays on an Exit reader. 
 
Sounder connected to a spare relay 
Diagram above shows Normally Open going Closed to trigger sound caused by an Input signal. 
Remember that the PCB legend applies when the PCB is powered OFF. 
When the PCB is powered the relay states become inverted 
9.5  Other AC2000 configuration options 
Access Levels  
For an S610S reader to function as part of an AC200 Access control system it is necessary to add 
the reader to a 
Group
 of readers that are part of an 
Access Level. 
A Valid Card swiped on a reader that is NOT in any Access level will cause  
the LDC to display WRONG ZONE.