Auxiliary Connections  
Auxiliary Connections 
The I/O plug-in board features a connector that includes two opto-coupled 
inputs and two relay outputs, as illustrated in Figure 10. 
 
 
jumper 
jumper 
jumpers 
jumpers 
relay 1  
relay 2 
input 1 
input 2 
 
 
 
 
 
connector to 
mother 
board 
relay output 1 
relay output 1 
relay output 2 
relay output 2 
 
input 1 - 
input 1 + 
input 2 - 
input 2 + 
 
Connection to LCD control board 
 
Figure 10: Auxiliary connections 
Note:  When the cables go externally, shielded cables must be used. The 
cable’s shield must be connected to ground connector 
You can define the operational mode of each relay by positioning the 
appropriate jumpers as follows: 
•  Jumper «OUT1» between 12 (NO) for relay 1 normally open 
•  Jumper «OUT1» between 23 (NC) for relay 1 normally closed 
•  Jumper «OUT2» between 12 (NO) for relay 2 normally open 
•  Jumper «OUT2» between 23 (NC) for relay 2 normally closed 
 
You can define the operational mode of each input by positioning the 
appropriate jumpers as follows: 
•  Jumpers «IN1» between 12 for input 1 on dry contact 
•  Jumpers «IN1» between 23 for input 1 opto-coupled 
•  Jumpers «IN2» between 12 for input 2 on dry contact 
•  Jumpers «IN2» between 23 for input 2 opto-coupled