Honeywell International Inc. RTU-B12 用户手册

下载
页码 30
LONWORKS( Data Cables 
Page 11 
 
 
 
L
ON
W
ORKS
 Data Cables 
 
•  The L
ON
W
ORKS
1
 data cable must be twisted pair 
•  In a free topology configuration, the sum total of the sections must not 
exceed 500m 
•  In a bus configuration, the sum total of the sections must not exceed 
2700m 
•  In a free topology configuration, activate the 50ohm terminator by placing 
the appropriate jumper on the FTT10A plug-in of the CTU-PLG06 board 
inside the TemaServer 
•  In a bus configuration, place two terminators (with resistance values of 
100ohm 1% ½W) at each end of the bus 
•  Check that the length of the L
ON
W
ORKS
 data cable corresponds to the 
norms indicated in Table 1. 
 
Type of cable 
Length [m] in relation to cable capacity 
AWG mm2 
Ohm/Km 50nF/Km 
100nF/K
200nF/K
500nF/K
1uF/Km 
12 3,3 5,7 
2676 
1892 
1338 
846 598 
14 2 8,8 
2153 
1523 
1077 
681 
482 
16 1,3 14 1707 
1207 
854 540 382 
18 0,9 21 1394 
986 697 441 312 
20 0,6 34 1096 
775 548 346 245 
22 0,35 52  886 626 443 280 198 
24 0,2 85 693 490 346 219 155 
Table 1: Length/capacity of L
ON
W
ORKS
 data cables (m) 
                                                           
1
 L
ON
W
ORKS
®
 is a trademark of Echelon Corporation