Honeywell International Inc. RTU-K12 用户手册

下载
页码 27
TemaKey TK C12  (RTU-K12 code 1500164xx) 
Page 25 
 
Inputs 
2 supervised or digital inputs. 
Mode select by JP2 
JP2 = Close Î Supervised inputs 
 JP2 = Open Î Digital inputs 
 
•  Supervised inputs with 4 status: 
normal, alarm, cut, short 
•  Digital inputs with status: open or Close  
 
Current 
0 to 10mA for each input 
 (internal 
reference 
5Vdc) 
Voltage +14V 
max. 
 
 
  0V 
min 
Outputs 
Number   
Type Power 
Open 
drain (MOSFET) 
Current 1,2A 
continuous 
 
5A (0,5sec) impulsive 
Voltage 
10V...+14V (internal Power 
 supply) 
Voltage (absolute max) 
10V...+30V  (from 
external Power supply). 
Current 1,2A 
[5A 
/ 0,5sec peak max – 
inductive  
load] 
Normality 
NO or NC via Jumper setting 
JP3 =  
1-2 OUT 1 NO 
 
2-3 OUT 1 NC 
JP5 =  
1-2 OUT 2 NO 
 
2-3 OUT 2 NC 
Wire length connection: it depends on cable 
diameter, load current sink and load min 
power supply 
On state resistance = typical  20 mOhm 
 
Load 1A = 0.02 V