The RTU is powered at low voltage (12VDC 160mA), preferably using a 
power supply module with battery backup (RTU-Qxx), or using an ordinary 
power supply having the same characteristics. The power cables must be 
dimensioned as indicated in the table below. The maximum allowable voltage 
drop on the power cable is 1V. 
•  Cable length(m) = 1V / (I[A] load x 2 x (res [Ohm/km] /1000)) 
Cabl e Type
Ext ensi on [ m]  based on l oad
AWG
mm2
ohm/ Km 160 [ mA] 320 [ mA]
12
3. 3
5. 7
548
274
14
2
8. 8
355
178
16
1. 3
14
223
112
18
0. 9
21
149
74
20
0. 6
34
92
46
22
0. 35
52
60
30
24
0. 2
85
37
18
 
The device is equipped with 2 non-removable cables of 3m length: 
•  Two-pole, twisted, unpolarized cable dedicated to the LON line 
connection 
-  LON 
 
   0,325 
mm
2
  white 
 
 
-  LON 
b    0,325 
mm
2
  orange 
•  Six-pole cable, providing the following signals: 
-  +12VDC 
 
   0,2 
mm
2
 red  
 
-  GND  
 
 
 
0,2 mm
2
 black 
 
-  INPUT 
   0,2 
mm
2
 brown 
-  INPUT 
   0,2 
mm
2
 orange 
-  OUT OC1    
  
 
0,2 mm
2
 yellow 
-  OUT OC2    
 
 
0,2 mm
2
 green 
 
The signals must be connected using a shunt box with IP protection level 
in conformance with the type of environment in which it is to be used: 
-  IP55 for moist environments 
-  Recessed box or IP31 at least for inside installations 
 
The shunt box must be positioned within the perimeter controlled by the 
access control system. 
The repeater relays must be inserted inside the box for electrical locking 
commands and the signal light. 