Honeywell International Inc. AZWDGL 用户手册
Installation and Operations Guide
|
AZW-5000
14
LTBT-TM-AZWIOG
Rev. 0001BETA
© Honeywell
Installation
This section explains how to mount and wire individual devices once they are
configured.
configured.
After all AZW-5000 devices are installed, ensure that only the coordinator is
wired to the primary BAS MS/TP network. Wiring multiple AZW-5000s to the
primary MS/TP network will cause routing loops.
wired to the primary BAS MS/TP network. Wiring multiple AZW-5000s to the
primary MS/TP network will cause routing loops.
WA R N I N G
Thoroughly read all instructions before mounting and wiring.
Install equipment in accordance with the National Electric Code, these
instructions, and in a manner acceptable to the local authority having
jurisdiction. Failure to do so can result in bodily injury or equipment damage.
instructions, and in a manner acceptable to the local authority having
jurisdiction. Failure to do so can result in bodily injury or equipment damage.
Mounting
Choose a mounting location that minimizes the amount of interference for radio
communication with the nearest node. Do not mount in a metal box or in a
fiberglass box impregnated with ferro magnetic` materials. Leave at least six
inches above the device for connecting wires and an external antenna (optional).
communication with the nearest node. Do not mount in a metal box or in a
fiberglass box impregnated with ferro magnetic` materials. Leave at least six
inches above the device for connecting wires and an external antenna (optional).
Some points to consider when selecting a location:
• The effective communication range is 50 feet (through two non-metal
walls).
• Any metal (ducting, equipment, metal studs, and so on) near the device
or between two devices will impede radio waves.
• If a wall has metal components (studs, ductwork, and so on) radio waves
will tend to travel along the plane of the wall. Mounting the device on
the same wall as other device(s) will increase signal strength.
the same wall as other device(s) will increase signal strength.
• When mounting near ductwork or other metal, use double-sided tape to
temporarily mount the device while testing radio reception.
• Mount the AZW-5000 indoors only.
DIN rail mounting
To mount the AZW-5000 on a DIN rail
1.
Hold the device with its top tilted toward the DIN rail and then hook the
two top tabs on the back of the device onto the top of the DIN rail.
two top tabs on the back of the device onto the top of the DIN rail.
2.
Push down and in to snap the bottom flex connector onto the DIN rail.
To remove the AZW-5000 from a DIN rail, push straight up from the bottom to
release the top tabs and then pull the top of the device outward.
release the top tabs and then pull the top of the device outward.
Wall mounting
To mount the AZW-5000 on a wall, position the device in any orientation and
secure it to the wall with size 6 or 8 screws appropriate for the mounting surface.
secure it to the wall with size 6 or 8 screws appropriate for the mounting surface.
Attaching an external antenna (optional)
The AZW-5000 has two internal antennas that will meet the requirements of
most applications. If you need additional range or if the device is mounted in an
most applications. If you need additional range or if the device is mounted in an