•   All Exciters in master/slave group are connected in series through 
their M/S and ground terminals using 20 AWG wire, as shown 
in the wiring diagrams.
For slave Exciters using their own ID numbers, the following is also 
required, as shown in Figure 3:
•   The mag lock (or elevator hold) outputs are wired to the relays 
on both the master and the slave to ensure that all doors in the 
vicinity will lock when a tag is present. 
•   Door contacts are wired together in series to the door contact 
input on both the master and the slave. The result is that when 
any door in a master/slave confi guration is open, the system 
behaves as if all doors are open: an alarm will occur if a tag is at 
a door in the vicinity of a door that is open.
Final Steps
Do not supply power to the Exciter or any other network 
device until all connections are complete.
Once all devices are installed, power up the Exciter and other devices. 
In the Hugs system software, run Auto Confi gure to install the new 
devices, and then confi gure them for operation.
The coverage area of each Exciter must also be checked.
Refer to the Hugs Installation Manual (p/n 805I0301) for 
detailed information on how to complete these steps.
Installing the Exciter
•  Ensure that the power supply and network are turned 
off to prevent electrical shock or damage to equip-
ment. 
•  Touch your hand to ground to discharge any electro-
static charge before handling the Exciter.
The steps below correspond to the numbers in Figure 1.
1
  Locate and record the LonWorks identifi cation number onto the 
facility fl oor plan indicating the Exciter’s position and network 
wiring path. Use the tear-away sticker on the Exciter’s Neuron 
ID label.
2
  Install the supplied door contact or PIR sensor according to the 
manufacturer’s instructions and connect it to the terminal, as 
shown in the wiring diagrams. Connect the LonWorks Network 
IN, Network OUT, and Power Supply to the terminal blocks, 
as shown in the wiring diagrams. If the Exciter is at the end of 
the network, then terminate the network segment with Item A 
(105 
Ω terminator). Refer to Detail A, and insert the terminals 
into the connectors on the Exciter.
 Note:
 If installing keypads or accessory devices, or if using a 
master/slave confi guration, proceed to the relevant sections on 
the opposite page, and then return to steps 3 and 4.
3
  Ensure that the status LED of the Exciter will be visible. Refer to 
the facility fl oor plan for location, and using the Exciter L-bracket 
as a template mark the location of the four mounting holes. Drill 
the holes.
Installing Keypads
A single keypad may be connected to an Exciter to enable an infant 
to be signed out at the door. The keypad also releases the Exciter’s 
relays, for example, to disengage a magnetic door lock. Hugs uses 
the Wiegand-standard KTP-103SN keypad, which offers individual 
passwords for each user.
Refer to the Hugs Installation Manual and the manufacturer’s instruc-
tions. Keypads may be connected to either master or slave Exciter.
Note:
The keypad requires a separate 12 VDC power supply.
Installing Accessory Devices
Each Exciter has two 30 VDC, 1 Amp, NO or NC relays for con-
trolling accessory devices, such as magnetic door locks and high 
output alarms.
Refer to the Hugs Installation Manual and the manufacturer’s instruc-
tions for installation procedures. Devices may be connected to either 
master or slave Exciters; connect devices to the master Exciter’s relays 
fi rst, then connect additional devices to the slave Exciter, starting 
with the closest.
Note: 
Accessory devices require their own power supply.
Master/Slave Installations
Master and slave Exciters are installed and connected to the Lon-
Works network in the same way as other Exciters, with the following 
additions: 
4
  Mount the Exciter.
L-bracket installations
A
  Install in the four mounting holes:
 
4 hollow wall anchors
B
  Attach the Exciter to the L-bracket, using:
 
4 No. 10 stainless steel machine screws
 
4 stainless steel hex nuts
 
4 No. 10 stainless steel fl at washers
C
  Attach the assembled Exciter and L-bracket to the previously 
installed hollow wall anchors, using:
 
4 No. 10 wood screws x 1 in. long
Surface mount installations
A
  Install in the four mounting holes:
 
4 hollow wall anchors
B
  Insert into the wall anchors, leaving 3/8 in. (0.5 cm) of the 
shaft exposed:
 
4 No. 10 wood screws x 1 in. long
C
  If using surface wire conduit, attach the four supplied 
bumpons (Item B in Figure 1) to the underside of the 
Exciter. 
D
  Align the Exciter with the mounting screws, and while lightly 
pressing, slide until it is securely in place. Insert the supplied 
screw caps.
Installation is complete. Proceed to Final Steps below.
Figure 2: Wiring for an Exciter and Range Extender (or a slave 
Exciter that uses the ID of the master)
Figure 3: Wiring for a master Exciter and a slave Exciter that uses 
its own ID number
Figure 1: Physical connections for the Exciter
Installing the Exciter
Installing Accessory Devices
Final Steps
Master/Slave Installations
Installing Keypads