Installing the Exciter
•  Ensure that the power supply and network are turned 
off to prevent electrical shock or damage to equip-
ment. 
•  Touch your hand to ground to discharge any electro-
static charge before handling the Exciter.
1
  Locate and record the LonWorks identifi cation number onto the 
facility fl oor plan indicating the Exciter’s position and network 
wiring path. Use the tear-away sticker on the Exciter’s Neuron 
ID label.
2
  Install the supplied door contact or PIR sensor according to the 
manufacturer’s instructions and connect it to the terminal, as 
shown in the wiring diagrams. Connect the LonWorks Network 
IN, Network OUT, and Power Supply to the terminal blocks, 
as shown in the wiring diagrams. Wrap the Power Supply cable 
around Item B (ferrite core); DO NOT use substitutes.
  
If the Exciter is at the end of the network, then terminate the net-
work segment with Item A (105 Ω terminator). Refer to Figure 
1
, and insert the terminals into the connectors on the Exciter.
 Note:
 If installing keypads or accessory devices, or if using a 
master/slave confi guration, proceed to the relevant sections on 
the opposite page, and then return to steps 3 and 4.
3
  Ensure that the status LED of the Exciter (located on the bottom 
of the case) will be visible. Refer to the facility fl oor plan for 
location, and using the Exciter  as a template mark the location 
of the four mounting holes. Drill the holes.
4
  Mount the Exciter:
A
  Install in the four mounting holes:
 
4 hollow wall anchors
B
  Insert into the wall anchors, leaving 3/8 in. (0.5 cm) of the 
shaft exposed:
 
4 No. 12 wood screws x 2 in. long
C
  If using surface wire conduit, attach the four supplied 
bumpons (Item B in Figure 1) to the underside of the 
Exciter. 
D
  Align the Exciter with the mounting screws, and while lightly 
pressing, slide until it is securely in place. Insert the supplied 
screw caps.
Installation is complete. Proceed to Final Steps below.
!
Installing Keypads
Refer to the wiring diagrams below and the manufacturer’s instructions. 
Keypads may be connected to either master or slave Exciter.
Notes:
•   Either one Wiegand or two Corby keypads can be connected to 
an Exciter.
•   The Wiegand and Corby keypads cannot be connected to the same 
Exciter.
•   The Wiegand keypad requires a 12 VDC power supply;  set the 
central Power Supply to 12 V for this application.
•   Corby keypads may be powered at 12 or 24 VDC. If connected at 
24 V, they require a 1 kW, 1/4 Ω resistor connected between the 
power supply and each keypad LED. Refer to Figure 2 below.
Installing Accessory Devices
Each Exciter has two 30 VDC, 1 Amp, NO or NC relays for con-
trolling accessory devices, such as magnetic door locks and high 
output alarms.
Refer to the wiring diagrams and the manufacturer’s instructions for 
installation procedures. Devices may be connected to either master 
or slave Exciters; connect devices to the master Exciter’s relays fi rst, 
then connect additional devices to the slave Exciter, starting with 
the closest.
Note: 
Accessory devices require their own power supply.
Master/Slave Installations
Master and slave Exciters are installed and connected to the Lon-
Works network in the same way as other Exciters, with the following 
additions: 
•   All Exciters in master/slave group are connected in series through 
their M/S and ground terminals using 20 AWG wire, as shown 
in the wiring diagrams.
For slave Exciters using their own ID numbers, the following is also 
required, as shown in Figure 2:
•   The mag lock (or elevator hold) outputs are wired to the relays 
on both the master and the slave to ensure that all doors in the 
vicinity will lock when a tag is present. 
•   Door contacts are wired together in series to the door contact 
input on both the master and the slave. The result is that when 
any door in a master/slave confi guration is open, the system 
behaves as if all doors are open: an alarm will occur if a tag is at 
a door in the vicinity of a door that is open.
Final Steps
Do not supply power to the Exciter or any other network 
device until all connections are complete.
Once all devices are installed, power up the Exciter and other devices. 
In the Xmark software, run Auto Confi gure to install the new devices, 
and then confi gure them for operation.
The coverage area of each Exciter must also be checked.
Refer to the Hugs Installation Manual (p/n 805I0301) for 
detailed information on how to complete these steps.
!
Figure 1: Wiring the terminal block
Installing the Exciter
Installing Accessory Devices
Final Steps
Master/Slave Installations
Installing Keypads