3)
 
Installation of two Model 240 readers back to back
For proper operation, readers installed back-to-back must be separated by at least 3.2 inches
(8cm).
Attention
Two readers may simultaneously read the same badge or tag if the distance between the two
readers is less than 6-inches (15 cm), back-to-back.
When using two readers back-to-back on a wall that will separate the two readers by 6 inches
(15 cm) or less, a metal plate (for example aluminium, 4-inches square (10cm x 10cm) must
be placed between the readers. To obtain the maximum read range, mount each Model 240
reader onto one or more Surface Mount Extension plates. Note the impact on badge read
range performance, as discussed in manual section, “Installation Considerations” (above).
Wiring
 Reader 12-position field wiring plug
Microcontroller
1
2
3
4
5
6
7
8
9
10
11
12
Micro control, reader beeper (option)
Ground
Power, 8VDC to 30VDC
Door Contact
Reader data
Exit Request (REX)
Green LED
Micro control, red LED (option)
RS-485-A, reader firmware maintenance
RS-485-B, reader firmware maintenance
Future
Future
Micro/5PX(N)
2RP and 8RP, see
Micro/5 manual.
DO NOT use the
Model 240 reader with
M/5-S2RP
Micro/PX-2000
Micro/PXN-2000
See micro manual
Micro/Reader-
Junction Box
See manual
Access Control system compatibility
The Model-240 badge reader will output a 16-digit badge identification (BID) number. As a result,
the Model-240 reader is only compatible with Picture Perfect access control systems. The Model-
240 reader is not compatible with Secure Perfect, Secure Perfect Enterprise Edition, SP, or SP-
Enterprise Edition access control systems, (12-digit BID number limitation).
Picture Perfect
A 16-digit BID format must be defined within Picture Perfect. Refer to the Picture Perfect On-line
help for assistance. In brief, go to Access / Badge Formats. Enter a suitable badge format
description, example: “16-digit BID” and define the format: “%16S” (omit the quote characters).
Reader to Micro wiring distance
The maximum reader to micro cable distance is 1,000 feet (305 meters) from the microcontroller