Please Read Before Installing
RF Lamp Dimmer
HRT-3LD
120/127 V~, 50/60 Hz
Installation Instructions
Overview
The HRT-3LD RF Lamp Dimmers are for use with
HomeWorks systems. The dimmer is used to provide
local control of table and floor lamps and integrate them
into the HomeWorks system.
HRT-3LD
Important Notes
Codes: Install in accordance with all local and national
electrical codes.
Danger: The Lamp Dimmer must not be used
to control equipment which is not visible from
every control location. It must also not be used
to control equipment which could create haz-
ardous situations such as entrapment if operated acci-
dentally. Examples of such equipment which must not be
operated by the Lamp Dimmer include (but are not limit-
ed to) motorized gates, garage doors, industrial doors,
microwave ovens, heating pads, etc. It is the installer’s
responsibility to ensure that the equipment being con-
trolled is visible from every control location and that only
suitable equipment is connected to the Lamp Dimmer.
Overheat Damage: To reduce the risk of overheating
and possibly damaging other equipment, do not install 
to control motor-operated appliances, transformer-sup-
plied appliances, or other non-lighting loads.
Environment: Ambient operating temperature: 
0-40°C, 32-104°F, 0-90% humidity, non-condensing.
Indoor use only. It is normal for a Lamp Dimmer to feel
warm to the touch during operation.
Lamp Type: Lamp Dimmers are designed for use with
incandescent, magnetic low-voltage, and tungsten halo-
gen lamps only. Do not use to control fluorescent lamps,
touch lamps, or lamps with an integral dimmer. For
lamps with integral 3-way switches, the switch should be
set to full on. Lamp Dimmers may not work with dioded
lamps (Sylvania Designer 16
TM
or Philips PAR-16
TM
).
Low-Voltage Applications: Use Lamp Dimmers with
magnetic (core and coil) low-voltage lamps only. Not for
use with electronic (solid-state) low-voltage transformers. 
Operation of a low-voltage circuit with lamps inoperative
or removed may result in transformer overheating and
premature failure. Lutron strongly recommends the fol-
lowing: 
a. Do not operate low-voltage circuits without operative
lamps in place.
1
b. Replace burned-out lamps as quickly as possible.
c. Use transformers that incorporate thermal protection or
fused transformer primary windings to prevent trans-
former failure due to overcurrent.
Load Specifications:
Control 
Min. Load 
Max. Load
HRT-3LD 
10 W/VA
300 W/VA
Cleaning:
To clean, wipe with a clean damp cloth. DO
NOT use any chemical cleaning solutions.
Cordset: Cordset length is 6 ft. (1.8m).
RF Device Placement: RF Lamp Dimmers must be
located within 30 ft. (9m) of an RF Signal Repeater or an
RF Processor. 
Setup: RF Lamp Dimmers cannot be controlled by the
system until they are addressed and programmed. See
the HomeWorks Utility online help.