Load Specifications
Control
Load Type
Min. 
Load
Max. 
Load
SZ-6D
1
Incandescent
40 W
600 W
MLV
2
40 W / VA
600 VA / 
450 W
SZ-6ND
1
Incandescent
10 W
600 W
MLV
2
10 W / VA
600 VA / 
450 W
SZ-5NE
1
SZ-6NE
SZ-6NA
Incandescent
5 W
500 W
ELV
2
5 W
500 W
SZ-6ANS
3
Lighting
10 W / VA
6 A
Motor
0.083 A
3 A
 
  Notes
1  
Dimmer Load Type: SZ-6D and 
SZ-6ND are designed for use with 
permanently installed incandescent, 
magnetic low-voltage (MLV), or 
tungsten halogen only. SZ-5NE is 
designed for permanently installed 
incandescent, electronic low-voltage 
(ELV), or tungsten halogen only. 
Dimmers cannot control motor-
operated equipment. Dimmers and 
switches cannot control standard 
receptacles. Contact Lutron for 
dimmable receptacle solution. 
2  Low-Voltage Applications: Use  
SZ-6D and SZ-6ND with magnetic (core 
and coil) low-voltage transformers only. 
Not for use with electronic (solid-state) 
low-voltage transformers.
Use SZ-5NE with electronic (solid-
state) low-voltage transformers only. 
Not for use with magnetic (core and 
coil) low-voltage transformers).
Operation of a low-voltage circuit 
with lamps inoperative or removed 
may result in transformer overheating 
and premature failure. Lutron strongly 
recommends the following: 
•  Do not operate low-voltage circuits 
without operative lamps in place.
•  Replace burned-out lamps as quickly 
as possible.
•  Use transformers that incorporate 
thermal protection or fused 
transformer primary windings to 
prevent transformer failure due to 
overcurrent.
3  Switch Load Type: SZ-6ANS is 
designed for use with all permanently 
installed lighting loads and with motor 
loads up to 1/4 HP (3 A).
Install in accordance with all local and 
national electrical codes.
Environment: Ambient operating 
temperature: 32 to 104 °F (0 to 40 °C),  
0 to 90% humidity, non-condensing. 
Indoor use only.
Spacing: If mounting one control above 
another, leave at least 4.5 in (114 mm) 
vertical space between them.
Faceplates: Use Lutron Stanza 
faceplates for best color match and 
aesthetic appearance. Do not paint 
controls or faceplates.
Cleaning: To clean, wipe with a clean 
damp cloth. 
Do NoT use any chemical 
cleaning solutions.
Wallboxes: Lutron recommends using 
3.5 in (89 mm) deep wallboxes for 
easier installation. Several controls may 
be installed in one multigang wallbox 
— see Derating Chart.
RF Device Placement: RF dimmers 
and switches must be located within  
30 feet (9 m) of an RF signal repeater or 
a device configured as a repeater.
Stanza RF dimmers or switches cannot 
be controlled by the system until they 
are addressed and programmed. They 
will work as stand-alone controls only.
Derating Chart 
Control
Load Type
End of 
Gang
Middle 
of Gang
SZ-6D, 
SZ-6ND
Incandescent
500 W
400 W
MLV
500 VA / 
400 W
400 VA / 
300 W
SZ-5NE
SZ-6NE
SZ-6NA
Incandescent
450 W
400 W
ELV
450 W
400 W
SZ-
6ANS
Lighting
5 A
3.5 A
Motor
3 A
3 A
 
Installation
WARNING - Shock hazard 
Wiring with power ON may 
result in serious injury or death. 
Locate and remove fuse or lock 
circuit breaker in the OFF position before 
proceeding. 
Short Circuit Check: Check the 
installation for short circuits before 
installing control(s). With power OFF, 
install standard mechanical switch(es) or 
wire connector(s) between hot and load. 
Restore power. If lights do not work or a 
breaker trips, correct wiring and check 
again. Install control(s) only when short 
is no longer present. Warranty is void 
if control is turned ON with a shorted 
circuit.
1.  Turn power OFF at fusebox or circuit 
breaker.
2.  Prepare wires. When making wire 
connections, trim or strip wallbox 
wires to the length indicated by the 
strip gauge on the back of the control.  
Note: Wire connectors provided are 
suitable for copper wire only.
   Wire Connector:
•  Use to join one 14 AWG (1.5 mm
2
or 12 AWG (2.5 mm
2
) ground wire 
with one 18 AWG (0.75 mm
2
) control 
ground wire.
Twist wire connector tight.  
Push-In Terminals: 
Insert wires fully. Push-in 
terminals are for use with 
14 AWG (1.5 mm
2
solid 
copper wire only. DO NOT 
use stranded or twisted wire. 
 
OR
Screw Terminals:  
Tighten securely to  
5 in•lbs (0.55 N•m).  
Screw terminals are for use 
with solid copper wire only
DO NOT use stranded or 
twisted wire.
3.  Wire controls as follows: 
Single location installation: See 
Wiring Diagrams 1 and 2. 
Power Booster and Interfaces: 
When using power boosters or 
interfaces, see wiring diagrams 
provided with the interface.
Ensure your customer will 
be happy by installing this 
product correctly so the 
tapswitch protrudes from  
the faceplate.
 4.  Push all wires back into the wallbox 
and 
loosely fasten the control to the 
wallbox using the control mounting 
screws provided. Do not pinch the 
wires.
•  For installation with a recessed 
wallbox, use spacer shims (Lutron  
PN 257117) for proper support of 
control(s).
•  For multigang installation, verify 
that the order of controls in the 
wallbox corresponds to the faceplate 
openings.
5.  Attach Lutron Stanza faceplate 
adapter and faceplate. 
  a.  Align the locating posts on the 
control(s) to the holes in the 
adapter.
  b.  Install the adapter onto front of 
control(s) using the short screws 
provided. The faceplate adapter 
should be firmly against the 
control.
  c.  Tighten control mounting screws 
until faceplate adapter is flush to 
wall (do not over-tighten).
  d.  Snap faceplate onto faceplate 
adapter, and verify that control is 
aligned properly and switch(es) 
protrude(s) in front of the faceplate.
  e.  If control(s) is (are) misaligned or 
switch(es) is (are) flush with the 
faceplate, loosen control mounting 
screws appropriately. 
6.  Restore power. Check for correct 
local operation (see Dimmer 
Operation and Switch Operation).
Installation Instructions
Please Read Before Installing
Stanza
TM
Stanza
TM
 Dimmers
SZ-6D, SZ-6ND
Stanza
TM
 Switch
SZ-6ANS
120 V~  50 / 60 Hz
Important Notes
Multigang Installations
Dimmer and 
Dimmer with Neutral
Switch
Middle of gang
End of gang
Control Location for Ganging
FCC Information
Changes or modifications not expressly approved by Lutron Electronics Co. could void the user’s authority to 
operate this equipment.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant 
to Part 15 of the FCC rules. Operation is subject to the following: (1) This device may not cause harmful interfer-
ence, and (2) this device must accept any interference received, including interference that may cause undesired 
operation.
FCC Information
Note: This equipment has been tested and found to 
comply with the limits for a Class B digital device, 
pursuant to Part 15 of the FCC rules. These limits are 
designed to provide reasonable protection against 
harmful interference in a residential and commercial 
installation. This equipment generates, uses and can 
radiate radio frequency energy and, if not installed and 
used in accordance with the instructions, may cause 
harmful interference to radio or television reception. 
However, there is no guarantee that interference will 
not occur in a particular installation. If this equipment 
does cause harmful interference to radio or television 
reception, which can be determined by turning the 
equipment off and on, the user is encouraged to try to 
correct the interference by one or more of the 
following measures:
•  Reorient or relocate the receiving antenna.
•  Increase the separation between the equipment and 
receiver.
•  Connect the equipment into an outlet on a circuit 
different from that to which the receiver is 
connected.
•  Consult the dealer or an experienced radio/TV 
technician for help.
Correct:  
Dimmer/switch protrudes 
from faceplate.
Incorrect:  
Dimmer/switch is flush 
with faceplate. Loosen 
control mounting screws.
STOP
Mounting Diagram
Control
Faceplate/adapter  
purchased separately.
Locating post
Faceplate adapter 
mounting screws
Control  
mounting screws
Locating post
Locating hole
Locating hole
English
In multigang installations, several controls are grouped horizontally in one multigang 
wallbox.
When combining controls in a wallbox, derating is required.