Lutron Electronics Company Inc 0118 用户手册

下载
页码 2
041588 
Rev. A
08/2018
PowPak 
|
 Installation
Control Module with 
EcoSystem
Test
Link
Cal.
+
For each system, ensure that you have:
One PowPak Control Module
At least one Wireless Transmitter
At least one 
EcoSystem
 LED Driver or Fluorescent Ballast
Required Components
Radio Powr Savr Occupancy/Vacancy Sensor 
(10 maximum)
Radio Powr Savr Daylight Sensor
(1 maximum)
Pico Remote Control
(10 maximum)
64 mA for the control lines. May be pre-installed in light fixture.
Note: All drivers and ballasts used with Vive wireless controls must comply with the 
limits for a Class A device, pursuant to Part 15 of the FCC rules.
PowPak Control Module with 
EcoSystem 
(1 maximum)
Raise
Toggle
Lower
Top LED
Consult third-party DALI fixtures installation guide for fixture-specific wiring. This device can 
be installed on a fixture / troffer, junction box, or marshalling box using the conduit nut or with 
mounting screws. The device must NOT be mounted inside a fixture / troffer or other metallic 
enclosure. Improper installation can result in degraded wireless communication, intermittent or 
sustained communication failures, and will not be covered under warranty. For mounting and 
wiring best practices see Lutron Application Note #620 (P/N 048620).
+
Occupancy Sensors
Daylight Sensor
Wireless Controls
Occupied: All lights 100%.
Unoccupied: All lights off.
Test
Link
Cal.
All lights dim in response to daylight.
On
All lights 100%
Favorite All lights 50%
Off
All lights off
Default Functionality
2
A
 The 
PowPak Control Module with 
EcoSystem
 
can be installed on a 
fixture / troffer, junction box, or marshalling box using the conduit nut 
(provided) or with mounting screws (not provided).
 Please consult local 
and national electric codes for proper installation.
B
  Once installed, energize the 
PowPak Control Module with 
EcoSystem
.
C
 
Use the Toggle “ u”  , Raise “▲” and Lower “
Δ
” buttons to verify
control wiring. 
English
All Wireless Transmitters must be installed within 
9 m 
(30 ft)
 of the 
PowPak Control Module with 
EcoSystem
.
EcoSystem
 Control: 18 V-  
64 mA
120 – 277 V~
  50 / 60 Hz  
80 mA
RMJS-ECO32-SZ
A  Connect mains wiring (
hot, neutral
) to each fixture.
Connect 
EcoSystem
 control to each fixture.
1
E1
E2
NEU
HOT
DALI
MAINS
To additional 
EcoSystem
 fixtures
Neutral
Line/Hot
E1
E2
+
WARNING! Shock Hazard. May result in serious injury or death. Turn off power at circuit 
breaker before installing the unit.
Sample LED 
driver shown
Important Notes: Please read before installing.
For installation by a qualified electrician in accordance with all local and 
national electrical codes.
• Use copper conductors only.
• Check to see that the device type and rating is suitable for the application.
• DO NOT install if product has any visible damage.
• If moisture or condensation is evident, allow the product to dry completely
before installation.
• Operate between 0 °C and 40 °C 
(32 °F and 104 °F)
 ambient.
• 0% to 90% humidity, non-condensing.
• For indoor use only.
Start Here
X
Vive
Programming with a Vive Hub
3
Mount, Wire, and Install 
EcoSystem
 
Devices and Lighting Fixtures
Consult third-party device installation guide
Install PowPak Control Module with 
EcoSystem
Suggested Installation Location: Center of room to 
ensure proper RF coverage of area.
 A 
 Use
 an
 iOS or Android compatible device.
 B 
 Download the Lutron Vive app.
 C 
 Open the app and follow the instructions.
Note: For further information on set up, programming, and troubleshooting with a Vive 
system, please refer to the installation instructions included with the Vive hub or visit 
www.lutron.com/vive
Note: For programming the 
PowPak Control Module with 
EcoSystem 
without a Vive hub 
see reverse side
.
Customer Assistance   www.lutron.com/support     
Troubleshooting
www.lutron.com /vive
Ballasts cannot be controlled locally from 
PowPak Control Module 
with 
EcoSystem
.
• Ensure that the breaker(s) to the
PowPak Control Module
 
are energized.
• Ensure that the
EcoSystem
 control lines are wired to the lighting fixture(s).
Reset to factory defaults.
Lights do not dim as expected.
• Ensure that
EcoSystem 
control lines are wired properly.
Lights do not respond to Wireless Transmitter(s).
Ensure that the breaker(s) to the PowPak Control Module with 
EcoSystem
 and drivers/ballasts are energized.
• Ensure that Wireless Transmitters are associated to the
PowPak Control Module with 
EcoSystem
.
Reset to factory defaults.
Lights are unstable at low-end or flash/flicker at turn-on or turn-off. • Adjust the low-end trim.
Wireless Transmitter(s) cannot be associated to 
PowPak Control 
Module with 
EcoSystem
.
• The maximum number of Wireless Transmitters have been associated to the
PowPak Control Module with 
EcoSystem
. To remove a previously set up Wireless
Transmitter, tap a Wireless Transmitter button three times; on the third tap hold for three seconds and then tap three more times.
Part of the Vive Family
vive.lutron.com
X
EcoSystem
 to Fixtures
E1
 (Violet)
E2
 (Violet/White)
Neutral (
White
)
Line / Hot  (
Black
)
Lutron Electronics Co., Inc.
7200 Suter Road
Coopersburg, PA 18036
041675 
Rev. A 
08/2018
Bottom LED
9 m
maximum
Radio Powr 
Savr Occupancy 
Sensor
Pico  
Remote  
Control
PowPak  
Control Module
Install in center of room  
to maximize RF coverage.
PowPak 
Control 
Module
Wire Gauge
Maximum DALI-compliant 
Bus Wire Length
1.5 mm
2
 (14 AWG)
300 m
0.75 mm
2
 (18 AWG)
150 m
0.5 mm
2
 (20 AWG)
100 m