Lutron Electronics Company Inc 0118 用户手册
041588
Rev. A
08/2018
PowPak
|
Installation
Control Module with
EcoSystem
Test
Link
Cal.
+
For each system, ensure that you have:
One PowPak Control Module
At least one Wireless Transmitter
At least one
EcoSystem
LED Driver or Fluorescent Ballast
Required Components
Radio Powr Savr Occupancy/Vacancy Sensor
(10 maximum)
Radio Powr Savr Daylight Sensor
(1 maximum)
Pico Remote Control
(10 maximum)
64 mA for the control lines. May be pre-installed in light fixture.
Note: All drivers and ballasts used with Vive wireless controls must comply with the
limits for a Class A device, pursuant to Part 15 of the FCC rules.
PowPak Control Module with
EcoSystem
(1 maximum)
Raise
Toggle
Lower
Top LED
Consult third-party DALI fixtures installation guide for fixture-specific wiring. This device can
be installed on a fixture / troffer, junction box, or marshalling box using the conduit nut or with
mounting screws. The device must NOT be mounted inside a fixture / troffer or other metallic
enclosure. Improper installation can result in degraded wireless communication, intermittent or
sustained communication failures, and will not be covered under warranty. For mounting and
wiring best practices see Lutron Application Note #620 (P/N 048620).
+
Occupancy Sensors
Daylight Sensor
Wireless Controls
Occupied: All lights 100%.
Unoccupied: All lights off.
Unoccupied: All lights off.
Test
Link
Cal.
All lights dim in response to daylight.
On
All lights 100%
Favorite All lights 50%
Off
Off
All lights off
Default Functionality
2
A
The
PowPak Control Module with
EcoSystem
can be installed on a
fixture / troffer, junction box, or marshalling box using the conduit nut
(provided) or with mounting screws (not provided).
(provided) or with mounting screws (not provided).
Please consult local
and national electric codes for proper installation.
B
Once installed, energize the
PowPak Control Module with
EcoSystem
.
C
Use the Toggle “ u” , Raise “▲” and Lower “
Δ
” buttons to verify
control wiring.
English
All Wireless Transmitters must be installed within
9 m
9 m
(30 ft)
of the
PowPak Control Module with
EcoSystem
.
EcoSystem
Control: 18 V-
64 mA
120 – 277 V~
50 / 60 Hz
80 mA
RMJS-ECO32-SZ
A Connect mains wiring (
hot, neutral
) to each fixture.
B
Connect
EcoSystem
control to each fixture.
1
E1
E2
NEU
HOT
DALI
MAINS
To additional
EcoSystem
fixtures
Neutral
Line/Hot
E1
E2
+
–
WARNING! Shock Hazard. May result in serious injury or death. Turn off power at circuit
breaker before installing the unit.
Sample LED
driver shown
Important Notes: Please read before installing.
For installation by a qualified electrician in accordance with all local and
national electrical codes.
For installation by a qualified electrician in accordance with all local and
national electrical codes.
• Use copper conductors only.
• Check to see that the device type and rating is suitable for the application.
• DO NOT install if product has any visible damage.
• If moisture or condensation is evident, allow the product to dry completely
• Check to see that the device type and rating is suitable for the application.
• DO NOT install if product has any visible damage.
• If moisture or condensation is evident, allow the product to dry completely
before installation.
• Operate between 0 °C and 40 °C
(32 °F and 104 °F)
ambient.
• 0% to 90% humidity, non-condensing.
• For indoor use only.
• For indoor use only.
Start Here
X
Vive
Programming with a Vive Hub
3
Mount, Wire, and Install
EcoSystem
Devices and Lighting Fixtures
Consult third-party device installation guide
Install PowPak Control Module with
EcoSystem
Suggested Installation Location: Center of room to
ensure proper RF coverage of area.
A
Use
an
iOS or Android compatible device.
B
Download the Lutron Vive app.
C
Open the app and follow the instructions.
Note: For further information on set up, programming, and troubleshooting with a Vive
system, please refer to the installation instructions included with the Vive hub or visit
www.lutron.com/vive
Note: For programming the
PowPak Control Module with
EcoSystem
without a Vive hub
see reverse side
.
Customer Assistance www.lutron.com/support
Troubleshooting
www.lutron.com /vive
Ballasts cannot be controlled locally from
PowPak Control Module
with
EcoSystem
.
• Ensure that the breaker(s) to the
PowPak Control Module
are energized.
• Ensure that the
EcoSystem
control lines are wired to the lighting fixture(s).
Reset to factory defaults.
Lights do not dim as expected.
• Ensure that
EcoSystem
control lines are wired properly.
Lights do not respond to Wireless Transmitter(s).
•
Ensure that the breaker(s) to the PowPak Control Module with
EcoSystem
and drivers/ballasts are energized.
• Ensure that Wireless Transmitters are associated to the
PowPak Control Module with
EcoSystem
.
Reset to factory defaults.
Lights are unstable at low-end or flash/flicker at turn-on or turn-off. • Adjust the low-end trim.
Wireless Transmitter(s) cannot be associated to
PowPak Control
Module with
EcoSystem
.
• The maximum number of Wireless Transmitters have been associated to the
PowPak Control Module with
EcoSystem
. To remove a previously set up Wireless
Transmitter, tap a Wireless Transmitter button three times; on the third tap hold for three seconds and then tap three more times.
Part of the Vive Family
vive.lutron.com
X
EcoSystem
to Fixtures
E1
(Violet)
E2
(Violet/White)
Neutral (
White
)
Line / Hot (
Black
)
Lutron Electronics Co., Inc.
7200 Suter Road
Coopersburg, PA 18036
041675
Rev. A
08/2018
Bottom LED
9 m
maximum
Radio Powr
Savr Occupancy
Sensor
Pico
Remote
Control
PowPak
Control Module
Install in center of room
to maximize RF coverage.
PowPak
Control
Module
Wire Gauge
Maximum DALI-compliant
Bus Wire Length
1.5 mm
2
(14 AWG)
300 m
0.75 mm
2
(18 AWG)
150 m
0.5 mm
2
(20 AWG)
100 m