Rosemount Tank Radar AB 5900 用户手册
Reference Manual
300520EN, Rev AA
November 2009
Rosemount 5900 Series
4-10
Section 4. Configuration
4.5.2
LPG
Configuration
Configuration
In the following description it is assumed that the Rosemount 5900 LPG
gauge is installed on the tank, and that a basic configuration is done as
described in the Rex II System Configuration Manual (Document no.
300510EN). Then it needs to be configured for LPG measurements. Do the
following:
gauge is installed on the tank, and that a basic configuration is done as
described in the Rex II System Configuration Manual (Document no.
300510EN). Then it needs to be configured for LPG measurements. Do the
following:
1. Ensure that the tank is empty.
2. Check that the ball valve (optional) on the gauge is open.
2. Check that the ball valve (optional) on the gauge is open.
In the TankMaster WinSetup work space choose the Logical View tab. Select
the icon that represents the radar level gauge, click the right mouse button
and choose LPG Setup.
the icon that represents the radar level gauge, click the right mouse button
and choose LPG Setup.
3. In the LPG Setup window click the Correction button.
Choose Air Correction Only from the list of correction methods and click the
OK button.
OK button.
NOTE!
The Air Correction Only option shall only be used when the tank atmosphere
contains air and no other gases.
The Air Correction Only option shall only be used when the tank atmosphere
contains air and no other gases.
When the LPG configuration is finished, the correction method needs to be
changed to a correction method that applies to the particular type of product
that is used.
changed to a correction method that applies to the particular type of product
that is used.
Correction
Preliminary