Using the Display Panel
5.4 Configuration
Output parameter
1.
Choose sub menu [1-1].
2.
Choose one of the following parameters to be displayed on the panel:
0: Level, 1: Ullage, 2: Volume (%), 3: Current, 4: Amplitude.
Antenna type
1.
Move to sub menu [1-2].
2.
Choose one of the following antennas:
0: 4 inch Horn Antenna.
1: 6 inch Horn Antenna.
2: 8 inch Horn Antenna.
Measurement Unit
1.
Choose sub menu [1-3].
2.
Choose one of the following options:
0: meter.
1: feet.
Tank Distances
1.
Choose sub menu [1-5] and enter the tank height R. Measure R from the
LoopRadar Reference Point to the tank bottom.
2.
If the Zero Level reference point is located above the tank bottom, choose
sub menu [1-6]. (This may be the case if for example a Datum Plate is
used).
In order to be able to measure levels below the Zero Level, enter the C
distance from the Zero Level to the tank bottom.
If C is set to 0, levels below the zero reference point will be presented as 0.
See chapter 4.1.2-3 for more information on the definition of tank geometry pa-
rameters.
Hold Off Distance
1.
Choose sub menu [1-7].
2.
Enter the Hold Off distance H. The Hold Off distance is defined as the dis-
tance from the LoopRadar Reference Point to the upper limit of the Ap-
proved Measurement Range.
See chapter 4.1 for further information on the definition of tank geometry.