Preliminary
ZUMMESH-JBOX
Zūm™ J-Box Load Controller
Installation Guide 
Description
The Crestron
®
 junction box-mounted zone controllers deliver intelligent lighting control 
with essential features for energy efficiency. Available for 20 A switching, 5 A or 16 A 
0-10 V dimming, and 20 A plug load control, each ZUMMESH-JBOX model wirelessly 
connects to Zūm daylight sensors, occupancy sensors, vacancy sensors, keypads, and 
dimmers (all sold separately) over the Zūm mesh network, providing intelligent lighting 
control based on the amount of natural light and the presence of people in a space. The 
Zūm J-Box Zone Controllers offer a powerful lighting control solution for every space 
within the Zūm network.
A basic single-room Zūm system consists of Zūm mesh devices, i.e., dimmers, switches, 
keypads, and sensors. The Zūm mesh devices in the room communicate directly with 
each other without the need for a centralized gateway or processor.
To monitor or control the room from a centralized Crestron control system, use the 
ZUMMESH-NETBRIDGE.
NOTE:  The ZUMMESH-NETBRIDGE requires a J-box device to provide power.
For quick network setup, use the Zūm app on a smartphone or tablet.
Additional Resources
Visit the product page on the Crestron website (www.crestron.com) 
for additional information. Use a QR reader application on your 
mobile device to scan the QR image.
Installation
WARNING:  To avoid fire, shock, or death, turn off the power at the circuit breaker or 
fuse and test that the power is off before wiring! 
NOTES:  Observe the following points:
  •  Install and use this product in accordance with appropriate electrical codes and 
regulations.
  •  A licensed electrician should install this product.
To install a switch or dimmer, do the following:
  1.  Turn the power off at the circuit breaker.
  3.  Mount the J-box device to the J-box.
  2.  Wire the device as shown in the following diagrams.
ZUMMESH-JBOX-5A-LV, ZUMMESH-JBOX-16A-LV, 
and ZUMMESH-JBOX-20A-SW Wiring
Test the Loads
Press the TEST button to toggle the connected loads. 
Press and hold the TEST button to cycle dim the connected loads (dimmer models only).
ZUMMESH-JBOX-PSU Wiring
NOTE:  The 0–10 V dim - and 0–10 V dim + wires are not present on the 
ZUMMESH-JBOX-20A-SW.
ZUMMESH-JBOX-20A-PLUG Wiring
SPECIFICATION 
DETAILS 
Power Requirements 
 
  Line Power 
100-277 Vac, 50/60 Hz 
  Idle State Power 
Consumption 
1 W 
Expansion Port 
Expansion port allows connection of an 
accessory such as a Z
ūm Network Bridge 
(ZUMMESH-NETBRIDGE) or HVAC Contact 
Closure Module (ZUM-CCO) 
SKUs  
 
  ZUMMESH-JBOX-16A-LV / 
ZUMMESH-JBOX-5A-LV 
 
     Switched Output 
 
16 A at 100-277 Vac, 50/60 Hz (20 A, de-rated  
to 80%) 
5 A at 100-277 Vac, 50/60 Hz 
     0-10V Output 
60 mA Sink or Source 
     DIM Load Type 
LED driver (4-wire), Fluorescent, Incandescent, 
MLV, ELV 
     Functionality 
Controlled by keypads, occupancy or vacancy, 
and daylight sensors. 
     Expansion Port 
Allows connection of Z
ūm Network Bridge or 
Relay Contact Closure Module 
  ZUMMESH-JBOX-20A-SW 
 
     Switched output 
 
20 A high in-rush (de-rated to 80%), zero cross 
switching 
     Switch Load Types 
0-10 V LED driver, Fluorescent ballast (4-wire), 60 
mA max current sink or source 
     Functionality: 
Controlled by keypads and occupancy or 
vacancy sensors 
     Expansion Port: 
Allows connection of Z
ūm Network Bridge or 
Relay Contact Closure Module 
ZUMMESH-JBOX-20A-PLUG 
 
     Switched output 
20 A high in-rush, zero cross switching for control 
of receptacles 
     Functionality 
Controlled by occupancy or vacancy sensors to 
energize receptacles when the room is occupied. 
Note that the output defaults to energized state 
after a power cycle. 
     Expansion Port 
Allows connection of Z
ūm Network Bridge or 
Relay Contact Closure Module 
  ZUMMESH-JBOX-PSU 
 
     Functionality 
Provides power for Z
ūm Network Bridge when 
other J-box devices are not available. 
     Expansion Port 
Allows connection of Z
ūm Network Bridge or 
Relay Contact Closure Module 
Enclosure 
 
  Housing 
Plastic, white, UL
®
 standard 5VA rated 
  Mounting 
Mounts in a 4˝ x 4˝ junction box via 1/2 in conduit 
knockout;  
Rated for mounting in plenum spaces, UL 
standard 2043 
Environmental 
 
  Temperature 
32° to 104 °F (0° to 40 °C) 
  Humidity 
10% to 90% RH (noncondensing) 
Dimensions 
 
  Height 
3.25 in (83 mm) 
  Width 
4.17 in (106 mm) 
  Depth 
1.31 in (33 mm) 
Weight 
0.4 lbs (7 oz) 
 
Neutral (white)
To 0-10 V 
Controlled load
0-10 V dim + (purple)
0-10 V dim - (gray)
Switched output (red)
Neutral
(white)
Hot (black)
100-277 Vac power 
from breaker
Neutral (white)
15 or 20 A receptacle
Switched output (red)
Hot (black) to 
unswitched 
receptacles
Neutral (white)
Hot (black)
100-277 Vac power 
from breaker
Neutral (white)
Hot (black)
100-277 Vac power 
from breaker