Installation Instructions
1 Smoke Detector Placement
On smooth ceilings, detectors may be spaced 9.1M (30 feet) apart 
as a guide. Other spacing may be required depending on ceiling 
height, air movement, the presence of joists, uninsulated ceilings, 
etc. Consult National Fire Alarm Code NFPA 72, CAN/ULS-S553-
M86 or other appropriate national standards for installation rec-
ommendations. 
Do NOT locate smoke detectors at the top of peaked or gabled 
ceilings; the dead air space in these locations may prevent the unit 
from detecting smoke.
Avoid areas with turbulent air flow, such as near doors, fans or 
windows. Rapid air movement around the detector may prevent 
smoke from entering the unit.
Do NOT locate detectors in areas of high humidity.
Do NOT locate detectors in areas where the temperature rises 
above 38ºC (100ºF) or falls below 5ºC (41ºF).
Install Smoke detectors in accordance 
with paragraph 2.1.1.1 of NFPA 72, 
Chapter 2.
“2-2.1.1.1 Smoke detectors shall be 
installed outside of each sleeping area in 
the immediate vicinity of the bedrooms and 
on each additional story of the family living 
unit, including basements and excluding 
crawl spaces and unfinished attics. In new 
construction, a smoke detector also shall be 
installed in each sleeping room.”
2 Mount Smoke Detector Backplate
Secure backplate to the mounting 
surface using the screws provided. 
Note: Avoid mounting on uneven sur-
faces or electrical boxes. Warping of 
the backplate can result in a tamper.
2 Install Batteries
Install batteries in the sequence indi-
cated. Use only 3 V
DC
 CR123A batter-
ies from the following approved 
sources:
Tekcell
Ever Ready
Panasonic
Mounting Holes
Locking
Tab
Insert
 First
Insert
 Last
4 Test Unit
The test can be initiated by pressing the test button or activating 
the internal reed switch with a magnet for a minimum of 5 sec-
onds. Alarm activation will be indicated by the flashing LED, The 
Sounder, and transmission of the alarm reporting code to the cen-
tral station. The detector will restore to normal after the test but-
ton is released or the magnet removed. 
Note: Allow a minimum of 20 seconds between test activations
Note: If the detector is in one of the following states when a test is 
initiated; it will not enter an alarm state.
1.
Tamper, (detector not installed on mounting plate).
2.
Compensation Trouble.
3.
Failure of Heat or Smoke detector.
4.
Other internal faults that could prevent a smoke or heat 
alarm
Device Enrollment
The 6 digit serial number located on the back of the smoke detec-
tor housing must be enrolled into the alarm control panel with 
Installer programming. Refer to the receiver Installation Manual 
for details.
Mounting
Detector Installation:
Position the detector on to the base 
plate using the detector and base 
plate alignment marks. Press the 
detector gently in place while rotating 
the detector clockwise until the detec-
tor snaps into place. Remove the side 
tab from the locking tab to lock in 
place.
Removal:
Depress tab with a small slotted 
screwdriver. Rotate detector counter-
clockwise until the alignment marks 
line up. Remove detector.
Compensation Reset
Cleaning, replacement of the smoke sensor, or other environmen-
tal changes may change the background signal/noise of the detec-
tor; this requires the drift compensation be reset. Compensation 
trouble is one of the faults indicated when the LED indicator is OFF 
while the sounder is chirping.
1.
Remove batteries
2.
Power up unit while pressing the test button.
The tamper switch must not be pressed.
3.
The LED will flash when 5 seconds has elapsed. Release the 
test button within 2 seconds of the LED flash.
4.
The LED will flash every 2 seconds  for 1 minute. During this 
period, the detector must be mounted. 
Allow an additional 2 minutes for the detector to make 
background level checks
5.
Test the detector to verify normal operation.