Controller Operation 
AYC-F/G/M60 Series Installation and Programming Manual 
33 
 
Secure 
A Secure user must have a Primary and Secondary code 
programmed; the two codes must not be the same. The Secure 
user can gain access when the unit is in any of its three modes of 
operation. In Normal mode, the Secure user must use the Primary 
code to gain entry. In Secure mode, the Secure user must present 
both the Primary and Secondary codes to gain entry. 
 
Master 
A Master user must have both Primary and Secondary codes 
programmed with the same code. The Master user can gain 
access during any mode of operation by presenting the PIN code 
and/or proximity card one time to the controller. (The Master user 
is convenient but is less secure than a Secure user.) 
5.2
 
Modes of Operation 
There are three modes of operation: 
5.2.1
 
Normal Mode 
The left LED is green. 
 
Normal mode is the default mode. In Normal mode, the door is locked 
until a Primary code is presented to the controller. Special codes such 
as Lock Strike code and Auxiliary code are active in Normal mode. 
(See Sections 
 5.9.3 and  5.9.4 for more information.) 
5.2.2
 
Bypass Mode 
The left LED is orange. 
 
In Bypass mode, access to the premises is dependent on whether the 
controller's Lock Strike Relay is programmed for Fail Safe Operation or 
Fail Secure Operation. When the Lock Strike is programmed for Fail 
Secure Operation, the door is locked until * is pressed. When the Lock 
Strike is programmed for Fail Safe Operation, the door is constantly 
unlocked. 
Orange 
Green