Rosslare Enterprises Ltd AYCF6X 用户手册

下载
页码 66
Controller Operation 
62 
AYC-F/G/M60 Series Installation and Programming Manual 
If the Programming code is valid, all memory is erased. You hear 
three beeps and the controller returns to Normal mode. 
If the Programming code is invalid, you hear a long beep and the 
controller returns to Normal mode without erasing the memory 
contents. 
5.9.17
  Replacing a Lost Programming Code 
 
The  unit must be in Normal mode; otherwise, this does not 
work. Make sure that the left LED is green before proceeding. 
1.
  Remove power from the power supply unit. 
2.
  Press the REX button on the power supply unit. 
3.
  Apply power to the unit with REX button pressed. 
4.
  Release the REX button. 
5.
  You now have 15 seconds to program a new Programming code 
into the access control unit using the default code based on the 
PIN code length you chose (see Table 4) before the controller 
reverts to the existing code. 
5.9.18
  Replacing a Lost Normal/Secure Code 
 
The  unit must be in Secure mode; otherwise, this does not 
work. Make sure that the left LED is red before proceeding. 
1.
  Remove power from the power supply unit. 
2.
  Press the REX button on the power supply unit. 
3.
  Apply power to the unit with the REX button pressed. 
4.
  Release the REX button. 
5.
  You now have 15 seconds to program a new Normal/Secure code 
into the access control unit using the default code based on the 
PIN code length you chose (see Table 4) before the controller 
reverts to the existing code.