Operating the HLX-24 
14 
HLX-24 User Manual 
3.5.5
 
Fire Alarm 
Fire alarm verification is an available option on fire zones. When used the 
system begins and Alarm Transmission Sequence once the conditions for fire 
alarm verification are met. 
 
The Fire Verify setting double checks the state of the fire detectors. 
When there is a fire sensor alarm signal, a siren is heard immediately. A 60-
second retard-reset period starts during which every additional fire alarm signal 
is ignored. After this period, an additional timeout of 60 seconds starts, which is 
the confirmation period, during which a fire sensor alarm signal causes an event 
transmission to the monitoring station. 
When the confirmation period expires, the fire zone is automatically restored 
and ready for a new fire alarm session.