Visonic Inc. DUETAM 用户手册

下载
页码 4
D-300431 
3
 
Applicable when DIP switch 3 is in ON position (anti masking ON): 
EOL
TAMP
TST
12V
24 H
TAMPER
ZONE
ALARM SYSTEM TERMINALS
BURGLAR
ZONE
9-16 VDC
OUTPUT
24 H
TROUBLE
ZONE
DUET-AM TERMINAL BLOCK
WALK
TEST
SWITCH
USING AN E.O.L. RESISTOR
WHEN THE CONTROL PANEL
IS SET FOR E.O.L. OPERATION
NC
BURGLAR
ZONE
EOL
EOL
RESISTOR
NC
NO/TRB
 
 
Applicable when DIP switch 3 is in OFF position (anti masking OFF): 
NC
NO/TRB EOL
TAMP
TST
12V
24 H
TAMPER
ZONE
ALARM SYSTEM TERMINALS
BURGLAR
ZONE N.C.
9-16 VDC
OUTPUT
DUET-AM TERMINAL BLOCK
WALK
TEST
SWITCH
USING AN E.O.L. RESISTOR
WHEN THE CONTROL PANEL
IS SET FOR E.O.L. OPERATION
NC
BURGLAR
ZONE
EOL
EOL
RESISTOR
BURGLAR
ZONE N.O.
 
Figure 6. Terminal Block Wiring 
IMPORTANT: To comply with CE safety requirements, connect to 
CE-approved control panels with current-limited DC output. 
 
Note: Use RTV to seal the base opening(s) to prevent insects from 
entering the detector. 
TST INPUT LOGIC  
The dual color LED may be enabled remotely for walk testing with a 
test switch connected to the TST input as shown in Figure 6: 
TST input grounded  -  LED active 
TST input floating or high (+12V) - LED inactive (unless mode 
switch 2 is ON). 
3.4 The Power-up Process 
After connecting the (+) and (–) terminals to the power source, the 
DUET-AM C/O starts a 60-second warm-up period, indicated by 
alternate flashing of the green and red lights. 
Caution! If the alternate flashing of the red and green lights does not 
stop within 60 seconds, a failure has been detected by the self-test 
circuitry or, if mode switch 3 is set to ON, the unit may be masked 
(refer to Para. 3.5).
 
3.5 What Happens in Case of Masking?
 
Attention! The following procedure is true only while mode switch 3 
is in the ON position. 
If an attempt is made to stick masking material over the lens or put 
a masking object close to the lens, a trouble alert will result about 60 
seconds after masking: 
 
The LED will flash red and green alternately; 
  The TRB relay will open and will remain so until masking is 
removed and the detector is reset (see Para. 3.13 for 
procedure). 
3.6 Visual Indications 
The dual color LED is used to signal various alarm and trouble 
messages as shown in Table 1 below: 
Table 1. Interpreting the Visual Indications 
Visual Indication  
Significance 
None  
  
No 
detection 
Steady green (5 seconds)    MW walk-test detection 
Flashing green 
 
 PIR walk-test detection 
Steady red (1.5-5 seconds)  Alarm: MW + PIR detection 
Flashing red and   
- Trouble is being detected (or  
green (alternately)  
masking if mode switch 3 is ON)  
 
 
 
- Initial warm-up routine (stops 60 
 
 
seconds after power up). 
Notes:  
1. During walk testing, the green light glows steadily (MW detection) 
or flashes (PIR detection), depending on which one of the two 
sensors discovered the movement first. Upon subsequent 
discovery of the movement by the other sensor, the green light 
goes off and the red light glows (alarm). 
2. If the LED maintains alternate red and green flashing beyond the 
warm-up period, a malfunction has been diagnosed (or, if mode 
switch 3 is ON, the detector may be masked).  
3.7 Mode Selector 
The DIP switch mode selector is mounted on the unit’s PC board 
(see Figure 4). It controls four functions as demonstrated in 
Figure 7.  
ON - 2 MOTION EVENTS
T RIGGER AN ALARM
OFF - 1 MOTION EVENT
TRIGGERS AN ALARM
ON
1
2
3
4
NOT USED
ON - LED PERMANENTLY
ENABLED
OFF - LED DISABLED -
ENABLED VIA TST INPUT
O N   -   A N T I - M A S K I N G
ENABLED. NO/TRB OUTPUT
OPERATES AS  NORMALLY
C L O S E D   T R B   O U T P U T.
O F F   -  A N T I   M A S K I N G
DISABLED. NO/TRB OUTPUT
OPERATES AS  NORMALLY
O P EN   A LA R M   O U T P U T.
 
Figure 7. DIP Switch Mode Selector 
Note: Switch positions shown are factory default. 
3.8 Vertical Adjustment 
The vertical adjustment scale for the PIR sensor is located at the 
upper right edge of the PC board (refer to Figure 4). Three  positions 
are available - FAR, MID and NEAR. All new DUET-AM C/O units are 
set to the FAR position.  
Note: For the optional  long range lens No. 34D, the vertical 
scale should be in FAR position. 
To adjust, loosen the vertical adjustment screw, slide the PC board 
along the vertical slot until the pointer indicates the required position 
on the scale (see Figure 8). When done, tighten the adjustment 
screw firmly.
 
 
Figure 8. Standard Lens Vertical Adjustment 
Caution!  With swivel brackets in use, the effective detection 
ranges may differ from those indicated in Figures 2 and 8. 
3.9 Setting the Motion Event Counter 
If you wish to set the PIR sensor for maximum false alarm immunity, shift 
DIP switch No. 1 (SW-1) to ON. In this position, two consecutive motion 
events are required to trip the PIR sensor. For faster catch performance, 
shift SW-1 to OFF. In this position, only one motion event is required to trip 
the PIR sensor.