3.4.3 
Connect Cabling for the Power Source 
1.  Run two DC power cables (#6 insulated red connected to -48 volts) and ground (DC 
return insulated black) from the site's -48VDC Distribution Panel (see Figure 3-17:  -
48 Volt Breaker Distribution Panel of the DC Power Supply - Red Wire
5
 and Figure 
3-18:  DC Return Distribution Bar - Black Wires) to each rack, attaching the cables 
to the racks. 
 
Figure 3-16:  DC Power Connection Found in Each Rack - Black (DC Return) and Red (-48 Volt) wires 
 
 
Figure 3-17:  -48 Volt Breaker Distribution Panel of the DC Power Supply - Red Wire 
                                                           
5
 The DC supply may not be the make shown here. 
Red 
–48VDC 
Black 
Return