Honeywell International Inc. 8DL5800PIR-OD 用户手册
5800-OD Wireless Outdoor Motion Sensor – Installation Instructions
–
4
–
SET THE SENSITIVITY
SET THE DIP SWITCHES
1.
Set the Sensitivity Select Switch to the desired
sensitivity.
sensitivity.
Sensitivity
Select Switch
(L,M,H)
Select Switch
(L,M,H)
Notes:
When greater sensitivity is desired, select "H".
When conditions are poor select "L".
1.
Set switch 2 for the desired
Battery Saving Timer
period.
Note: The alarm output
activations are limited by
the timer selection (5 or
120 seconds). Even if there
are continuous alarm
events, the alarm output
operates only once in the
selected timer period. This
can be 5 or 120 seconds.
120s – Default Setting
5s – Used when frequent
alarm transmission is re-
quired. Battery life will be
shortened when using this
setting.
Battery Saving Timer
period.
Note: The alarm output
activations are limited by
the timer selection (5 or
120 seconds). Even if there
are continuous alarm
events, the alarm output
operates only once in the
selected timer period. This
can be 5 or 120 seconds.
120s – Default Setting
5s – Used when frequent
alarm transmission is re-
quired. Battery life will be
shortened when using this
setting.
2.
Set switch 3 for the desired Pulse Count
(selectable for 2 or 4).
(selectable for 2 or 4).
Pulse Count of 2 = detection can be made with
as little as two steps.
Pulse Count of 4 = detection can be made with
as little as four steps.
as little as two steps.
Pulse Count of 4 = detection can be made with
as little as four steps.
3.
Set switch 1 to enable the Walk Test, see the
instructions below.
instructions below.
ON 1. Walk Test
5s 2. Battery Saving Timer
2 3. Pulse Count
ON
1
2
3
OFF
120s
4
6
Perform a Walk Test
NOTE:
With the Walk Test switch set to ON the LED will light when the detector is tripped, and the alarm is generated instantly.
1.
Set the walk test
switch (DIP switch
1) to ON. Replace
the cover.
switch (DIP switch
1) to ON. Replace
the cover.
2.
Perform a walk test
through the
detection area, and
verify satisfactory
results.
through the
detection area, and
verify satisfactory
results.
3.
Allow the detection
area to remain
static and check for
false or unwanted
detections.
area to remain
static and check for
false or unwanted
detections.
4.
If necessary, adjust
the detection area
(see Perform Settings
& Adjustments).
the detection area
(see Perform Settings
& Adjustments).
5.
Repeat the walk test
through the detection
area, and verify
satisfactory results.
through the detection
area, and verify
satisfactory results.
6.
Set the walk test
switch to OFF, and
secure the Cover with
the Captive Lock
Screw.
switch to OFF, and
secure the Cover with
the Captive Lock
Screw.
Notes:
If normal car or people
traffic pass close to the
detection area, adjust the
detection area 1.5 to 2.0m
(5 to 7ft) shorter to reduce
false detections. This also
allows for changes due to
environmental thermal
conditions.
traffic pass close to the
detection area, adjust the
detection area 1.5 to 2.0m
(5 to 7ft) shorter to reduce
false detections. This also
allows for changes due to
environmental thermal
conditions.
If the detection length is
adjusted to position "A"
[12m (40ft)], the detection
area may increase when
there is a big temperature
difference between the
moving object and the
background.
adjusted to position "A"
[12m (40ft)], the detection
area may increase when
there is a big temperature
difference between the
moving object and the
background.
If this causes a problem, adjust the detection length
to position "B". Then walk test to verify satisfactory
results.
to position "B". Then walk test to verify satisfactory
results.
Approx.8m (27ft)
position B
Approx.12m (40ft)
WALK TEST
This sensor has a multi-
level detection pattern
(from side view). A heat
source beyond the
detection area may cause
the detector to issue a
false alarm by reflecting
off the ground. Examples
include puddles, wet
surfaces, very smooth
asphalt or concrete
surfaces.
level detection pattern
(from side view). A heat
source beyond the
detection area may cause
the detector to issue a
false alarm by reflecting
off the ground. Examples
include puddles, wet
surfaces, very smooth
asphalt or concrete
surfaces.
If this causes a problem,
adjust the detection
length to position "B".
Then perform a walk test
to verify satisfactory
results.
adjust the detection
length to position "B".
Then perform a walk test
to verify satisfactory
results.
7
Program the Control Panel
Prior to use in the system, you must “enroll” the transmitter's serial number in the control panel. Refer to the control panel’s instructions for
further details. During programming, the transmitter shall be treated as RF supervised . (Mandatory for UL installations.)
further details. During programming, the transmitter shall be treated as RF supervised . (Mandatory for UL installations.)
TROUBLESHOOTING
SYMPTOM
CAUSE
REMEDY
Batteries are incorrectly installed or
dead.
dead.
Check for correct battery installation, or replace dead
batteries.
batteries.
No detection, when walking
through the detection area.
through the detection area.
Wiring is faulty or loose.
Check all connectors and wiring.
Water in unit.
Check for cracks in the housing that would allow water
infiltration. Replace unit.
infiltration. Replace unit.
Transmitter or PIR sensor is faulty.
Replace unit.
No detection occasionally, or poor
detection.
detection.
Sensitivity is set too low.
Try a higher sensitivity setting.
Detection area is not set correctly.
Perform a Settings & Adjustments procedure.
Low battery fault indicated on
system keypad display.
system keypad display.
Batteries are very low or dead.
Replace batteries.