UTC Fire & Security B.V. ATS111X 用户手册

下载
页码 8
2
  AL-111X Arming Station
 Mounting the RAS
1.
Attach the mounting plate to the mounting surface using the three screws provided.
2.
Ensure that the back tamper switch (see Figure 1) can rest on a flat surface flush with the back of the mounting
plate (avoid rough or non-flat surfaces).
3.
If rear cable entry is used (through the mounting plate), cut a hole in the mounting surface for cable access.
4.
Set the RAS address using DIP switches 1 through 4 (see DIP Switch Settings).
5.
Set the COMMS (System BUS) termination switch using DIP switch 5, if required.
6.
Terminate the COMMS (System BUS) cabling.
Note 
 All power should be turned off to the control panel before wiring the RAS.
7.
Insert plastic cable entry blanking plugs (provided) into the back of the RAS to blank any unused cable entry
channels (see Figure 1).
8.
Place the RAS onto the mounting plate and lock in place by moving the unit down by about 0.3 inches (8mm).
9.
Tighten the locking screw at the base of the RAS till firm. Do not over-tighten.
Tamper Switch
The back tamper switch (see Figure 1) must be sealed for the system to work correctly. Make sure that the tamper switch
rests on a surface so that it remains depressed when the RAS is mounted. If the unit is tampered with the tamper switch
should spring open.
In operation, the LCD display will show “RAS Tamper” when not sealed.
Removing the Cover and Mounting Plate
The RAS cover is hinged at the bottom. To open, grasp the cover at the sides or the top and pull gently - the cover will
swing down on its pins (see Figure 1). The cover may be fully removed by gently prizing one of the pins away from the
body of the RAS and pulling.
The metal mounting plate at the back is held by a locking screw (see Figure 1). To remove the mounting plate, loosen the
screw by at least 8mm (0.315 in.), slide the mounting plate down, and then pull the bottom of the mounting plate away from
the body of the RAS.
 DIP Switch Settings
DIP switches are located on the back of the RAS (see
Figure 1) and are used for setting the RAS address and the
System BUS termination (TERM) condition.
RAS Address Switches
Use switches 1 to 4 to set the RAS address (as well as the
reader address for AL-1115 and AL-1116). See Figure 3.
TERM Switch
Use switch 5 (see Figure 2) to set the TERM (System BUS
termination) to “ON”, if needed.
There must be no more than two TERM switches or links
set to “ON” for any System BUS. Refer to the control
panel installation guide for details about the use of TERM
switches or links.
Figure 3. RAS Address DIP Switch Settings
Switch toggles are indicated as black.
Example: RAS 1 = Off, Off, Off, Off
All switches shown in
the OFF position
RAS Address  TERM
 1    2    3    4    5
ON               ECE
Figure 2. DIP Switches