Installation Instructions for: 
 Model: 
SU-2-00  
Installation Materials Supplied  
 
SU-2 Sensor Unit  
 
Anchor Screw 
 
Caution  
 
Disconnect all power before installation or service.  
 
All installations and maintenance work must be performed by 
qualified personnel.  
 
The SU-2 must be installed in accordance with state, local and 
national electrical codes and requirements.  
 
 
 
 
Installation Instructions for SU-2-00
 
 
1.  Turn off all power to the light fixture by switching off the circuit 
breaker. 
2.  The RJ11 data cable should already be installed and connected to 
the CU-2 mounted in the ballast cavity of the fixture or mounted in a 
UL approved enclosure.
 
 
3.  The SU-2 Sensor should be mounted to the ceiling within a few feet 
of the lighting fixture and over the service area of the light. 
4.  Select a place for the RJ11 data cable to exit the plenum and make a 
small cut in the ceiling tile for the cable to exit. 
5.  Install the SU-2 anchor screw (as shown). 
6.  Connect the RJ11 data cable to the Sensor (bottom entry). 
7.  Slide the SU-2 onto the screw head as shown.  
8.  Slip the excess RJ11 data cable up into the plenum area and adjust the ceiling tile to the original position.