•  Do not install detectors in the following areas:
•   In or near areas where particles of combustion are normally present such as 
kitchens, in garages, near furnaces, hot water heaters, or gas space heaters.
•   In very cold or very hot areas that may be outside the detectors op-
erating range.
•   In wet or excessively humid areas, or next to bathrooms with showers.
•  In dusty, dirty, or insect-infested areas.
•   Near fresh air inlets or returns or excessively drafty areas.
 
Air con-
ditioners, heaters, fans, and fresh air intakes and returns can drive 
smoke away from the detector.
INSTALLATION
Add the CO/Smoke Detector to the TouchScreen:
1.   Remove detector from packaging and separate the mounting base from 
the detector head.
2.   On the TouchScreen, log into the Settings app with an Installer code.
3.   Enter Technician Code/ID.
4.   In the Settings menu, tap Sensors & Zones > Add a Sensor/Zone. 
5.   Remove the battery tab from the detector, making sure the batteries re-
main fully seated. The detector will run through its initialization. (See 
Table 1.) 
6.   The base model will enter Search mode (skip to step 8). The voice model 
will prompt for language selection. (Move to step 7.)
7.   Press the Smoke test button to select English or the CO test button to se-
lect Spanish language settings. Once the language is selected the detector 
will enter Search mode. (To reset language selection, see Restore Factory 
Settings section.)
8.   At the Locating Wireless Sensors screen, tap Next. A Done button ap-
pears on the screen and the TouchScreen searches for sensors that are 
available to be added. As sensors are found, a grayed icon appears for 
that sensor. It will indicate a Trip to Pair operation request. The tamper 
feature is disabled at this time to allow time to install the detector and 
mounting bracket on the ceiling or wall. 
9.   A sensor that has been automatically enrolled will appear on the screen 
with a green check mark. If after waiting 15 seconds a green check mark 
does not appear, press the respective test button to pair the sensor to the 
TouchScreen. Press a test button to vocalize the signal strength status 
between sensor and panel. 
10.   Any located sensors that were not paired are released by the TouchScreen 
and can be added later. The Wireless Sensors Located screen shows the 
number of wireless sensors found and paired. 
11.   Upon success pairing of both CO and Smoke sensors, tap Done, tap Next. 
The Configure Wireless Sensors screen shows icons of the sensors that 
were found and paired. Touch each sensor icon to configure the corre-
sponding device. 
12.   The Add Sensor/Zone Modify screen appears. To change the Smoke Icon 
or CO Icon (if multiple options are available) and the 24-Hour zone func-
tion, tap the drop down arrow next to the value you wish to modify, and 
then select the new value from the choices provided. 
13.   The Add Sensor/Zone Modify screen appears. To modify a Zone Label on 
the TouchScreen, tap the field, use the onscreen keyboard to enter your 
changes, and tap Done to save your changes.
14.   Tap Next in the Add Sensor/Zone screen. If all of the sensors have not 
been configured, the Modify screen appears for each sensor to let you 
review its details. Change the details as needed or tap Next to cycle 
through all sensors. The sensors are marked as configured. 
MOUNTING
Physically mount the smoke detector in the desired location; 
NOTE: NFPA 72 recommends the installation of detectors only after complet-
ing construction or any other dust producing activity. 
Smoke detectors are not to be used with detector guards unless the combina-
tion has been evaluated and found suitable for that purpose.
1.   Disconnect alarm-notification appliances, service-release devices, and 
extinguishing systems.
2.   Hold the smoke detector where you plan to install it. If the green LED is 
blinking rapidly while off its mounting base, this indicates the RF signal 
strength is adequate. Press a test button and verify the signal strength.
3.   Using two supplied screws and anchors, mount the base. 
4.   Attach the smoke detector to the mounting base with a clockwise mo-
tion. 
5.   Test each detector as described in the Testing section.
6.   Notify the proper authority that the system is in operation.
TESTING
Test communications between the detector and the control panel; 
The detector has two test buttons; one for smoke testing and one for CO test-
ing. The detector may also be functionally tested using canned smoke and 
canned CO. If the detector fails any of the test methods the detector should 
be replaced.
NOTE: Testing the detector will activate the alarm and send a signal to the 
panel. Before testing, notify the proper authorities to avoid any nuisance 
alarms. 
1.   Pressing the Smoke test button for 1 second will provide audible diag-
nostic information for the homeowner on sensor status and battery life. 
Pressing and holding the Smoke test button for 3 to 5 seconds will pro-
vide diagnostic information for the technician including smoke sensitiv-
ity readout and then enter smoke entry test mode. (See Smoke Entry Test 
section.)
2.   Pressing the CO test button for 1 second will provide diagnostic informa-
tion for the homeowner on sensor status, battery life, and CO sensor life. 
Pressing and holding the CO test button for 3 to 5 seconds will enter 
functional gas entry test mode. (See Functional Gas Test section.) 
3.   The control panel alarm and all auxiliary functions should be verified for 
a complete test of the system. 
TABLE 1: OPERATION MODES
MODE
STATUS LED (TOP)
LED 
WINDOWS 
(SIDE)
SOUNDER
SPEAKER
POR out-of-box
Blink  
red-green-amber
Dark
Silent
Voice welcome, instructions follow POR for language selection
POR
Blink green,  
2 seconds when  
boot is complete.
Dark
Silent
Silent
Enrollment
Blinks green  
every 5 seconds
Dark
Silent
Annunciates Enrollment Successful along with signal strength, or 
enrollment failed after 2 minutes.
Tamper Mode  
(Enrolled with panel, not mounted on base)
Blink amber  
every 10 seconds
Dark
Silent
Voice signal strength annunciation with a press of the test button.
Standby (Mounted on Base)
Blink green  
every 10 seconds
Dark
Silent
Silent
Smoke Alarm
Blink red
Blink red
Temp-3
Voice smoke warning
CO Alarm
Blink red  
every 10 seconds
Blink blue
Temp-4
Voice CO warning
Powered Down
Dark
Dark
Silent
Silent
  