Andrew Wireless Innovations Group RPT-NODEC843 用户手册

下载
页码 102
 
User’s Manual for Node C Network Elements
 
Page 22 
 M0121A1A_uc.doc
 
3.2.3 Power 
Connection 
  
Before connecting electrical power to the units, the system must be grounded as 
described in the previous chapter. 
 
Mains power must be connected at the mains connector of the Interface Unit. The 
power supply plug is included with the Node C. 
 
 
The correct wiring 
of the power supply 
plug is as follows: 
 
figure 3-10 Power supply plug 
figure 3-11 Mains connector 
 
 
A minimum cross section of 1.5 mm
2
 is required for the power supply 
connection. Each wire must observe the applicable national regulations 
regarding loop impedance, voltage drop, and methods of installation. 
Make sure to connect the correct voltage to the unit. 
 
)
 Note:  Do not connect or disconnect the power cord at the mains connector 
while power is on. Turn off mains* power before connecting the 
power cord at the Interface Unit, then, engage mains again. 
* Mains power must be interrupted with an external AC breaker. For the AC breaker, 
observe the following recommendation: 
 
120 Volt / 20 Amp max. or 240 Volt / 16 Amp, single-phase, 50/60 Hz AC service is 
needed, i.e. the external AC breaker should be 20 Amps max. for 120-Volt service or 
16 Amps for 240-Volt service.  
 
Mains