Threshold
Selects the threshold value that will be used to detect the error condition. This doesn’t
apply to the PLL Lock Fail alarm.
Pin Polarity
Selects whether the alarm output pin is active high or active low. When +ve is selected,
the output will act as a 430 Ohm resistor to ground when the alarm is active and as a 100
KOhm resistor to ground when the alarm is not active and vice-versa if -ve is selected.
On Delay
Selects how long the failure condition must be present for before the alarm is fired. This
can be set from 2 seconds to 600 seconds.
Off Delay
Selects how long the failure condition must have stopped for before the alarm is re-
leased. This can be set from 2 seconds to 600 seconds.
Send e-mail
Selects if an e-mail will be sent when the alarm state changes. Ensure that the unit is
connected to the network and that E-mails have been set up correctly System
⇒ E-
Mail to use this feature.
Examples of alarm uses and set-up
Example 1: We would like the system to fire alarm A with normal polarity when the forward
power has dropped below 40.5 watts for longer than 20 seconds. We would like the alarm to
be release if the power rises above 40.5 watts for longer than 10 seconds.
Setup:
1. Navigate to Alarms
⇒ Alarm A
2. Select Type Alarm
3. Select Source Fwd Power <
4. Set Fwd Power Threshold to 40.5W
5. Set Pin Polarity to +ve
6. Set On Delay to 20s
7. Set Off Delay to 10s
8. Set Send e-mail as required. Make sure emails are set up correctly if the feature is en-
abled (consult the relevant section in this manual)