EMC Directives
4 – 8
D101583 0207
BL ident
The following must be observed:
„
As the interference signals are frequently in a range > 10 kHz, a 
large area shield connection is necessary.
„
The shield bar is very conductive and connected over a large 
area with the switch cabinet housing and must be as near as 
possible to the cable entry. The cable must be stripped and 
connected to the grounding bar with an RF clip or cable tie.
„
The shielding bar must be connected with the PE bar.
„
If shielded cables have to be interrupted, the shield must 
continue via the corresponding connector housing using 
suitable connectors.
„
If intermediate connectors are used which do not feature a 
suitable shield, the shield must be connected via cable clips to 
the point where it is interrupted.