Energy Intelligence Solutions
PE1216/PE1324
Energy PDU
Specification
Features
The PE1216/PE1324 Energy PDU contains 16/24 AC outlets and
is available in IEC or NEMA socket configurations. The PE1216/
PE1324 Energy PDU features a space-saving 0U design that
allows it to be mounted vertically on the outside of a rack,
resulting in a more efficient use of space in the server room,
while providing 16/24 AC outlets.
is available in IEC or NEMA socket configurations. The PE1216/
PE1324 Energy PDU features a space-saving 0U design that
allows it to be mounted vertically on the outside of a rack,
resulting in a more efficient use of space in the server room,
while providing 16/24 AC outlets.
The PE1216/PE1324 Energy PDU can be integrated into an
installation with the EC1000 Energy Box
installation with the EC1000 Energy Box
*
, allowing you to
monitor the real-time current and environmental conditions of
the Energy PDU from the front panel of the EC1000 at the rack,
or via Web GUI remotely – making your server room efficiently
green with ease.
the Energy PDU from the front panel of the EC1000 at the rack,
or via Web GUI remotely – making your server room efficiently
green with ease.
* ATEN EC1000 Energy Box and energy management software – eco
Sensors are available at www..aten.com.
• Space saving 0U rack mount design
• IEC or NEMA outlet models
• Real-time PDU current monitoring
• IEC or NEMA outlet models
• Real-time PDU current monitoring
*
* When used in conjunction with the EC1000 Energy Box
Function
PE1216A
PE1216B
PE1216G
PE1324B
PE1324G
Power Outlets Direct
16 x NEMA 5-15R
16 x IEC C13
16 x IEC C13
24 x IEC C13
24 x IEC C13
Connectors
Inlet
1 x IEC60320 C20
1 x IEC60320 C20
1 x IEC60320 C20
1 x NEMA L6-30P
1 x IEC 60309
32A
Energy Sensor
Port
1 x RJ-45 Female
2 x RJ-45 Female
Nominal Input Power
100-120V~, 50/60Hz,
20A(Max), 16A( UL de-
rated)
100-240V~, 50/60Hz,
20A(Max), 16A( UL de-
rated)
100-240V~,
50/60Hz,16A(Max)
100-240V~, 50/60Hz,
30A(Max), 24A( UL de-
rated)
100-240V~,
50/60Hz, 32A(Max)
Nominal Output Power
100-120V~, 50/60Hz
Per Outlet 15A (Max),
12A( UL de-rated)
Total : 20A(Max),
16A( UL de-rated)
100-240V~,50/60Hz
Per outlet 15A (Max),
12A( UL de-rated)
Total : 20A(Max),
16A( UL de-rated)
100-240V~,50/60Hz
Per Outlet 10A (Max)
Total : 16A(Max)
100-240V~,50/60Hz
Per bank 15A (Max),
12A ( UL de-rated )
Total : 30A(Max),
24A(UL de-rated)
100-240V~,50/60Hz
Per bank 16A (Max)
Total : 32A(Max)
Environment
Operating
Temp.
0 – 50˚C
Storage Temp.
-20 – 60˚C
Humidity
0 – 80% RH, Non-Condensing
Physical
Properties
Housing
Metal
Weight
1.31 kg
1.31 kg
1.23 kg
3.47 kg
3.47 kg
Dimensions
( L x W x H )
73.00 x 4.40 x 4.40 cm
68.00 x 4.40 x 4.40 cm
134.00 x 4.40 x 4.40 cm
PE1216
PE1324
EC1000