10.4. Configuring periodic variables 
This window is used to configure the IO Scanning function, described in the IO Scanning 
Service section on page 72. 
Example: 
•The periodic variables of the drive at IP address 192.168.1.12 are associated with PLC 
data words. 
•The drive periodic output variables (control) are associated with the 32 words (WR 
count) starting at PLC address %MW550 (Write Ref.). 
•The drive periodic input variables (monitoring) are associated with the 32 words (RD 
count) starting at PLC address %MW500 (Read Ref.).   
 
The addresses for the PLC %MW words correspond to the configuration in the previous example. 
 
 
 
 
 
 
 
 
PLC 
address 
Periodic output variable 
(default assignment) 
Configurable 
%MW 550 
Reserved   
No 
%MW 551 
Scanner write word 1   
Yes (c001) 
%MW 552 
Scanner write word 2   
Yes (c002) 
%MW 553 
Scanner write word 3
 
Yes (c003) 
%MW 554 
Scanner write word 4 
 
Yes (c004) 
%MW 555 
Scanner write word 5   
Yes (c005) 
%MW 556 
Scanner write word 6   
Yes (c006) 
%MW 557 
to 
%MW 581 
Reserved No 
 
PLC 
address 
Periodic output variable 
(default assignment) 
Configurable 
%MW 500 
Reserved   
No 
%MW 501 
Scanner read word 1   
Yes (c021) 
%MW 502 
Scanner read word 2   
Yes (c022) 
%MW 503 
Scanner read word 3
 
Yes (c023) 
%MW 504 
Scanner read word 4 
 
Yes (c024) 
%MW 505 
Scanner read word 5   
Yes (c025) 
%MW 506 
Scanner read word 6   
Yes (c026) 
%MW 507 
to 
%MW 531 
Reserved No