MAINTENANCE, CARE & CLEANING
TEMPERATURE CONTROL ADJUSTMENT FOR 
HIGH ALTITUDE ONLY!
TERMS:
Cut-out - Temperature sensed by the 
controller that shuts the compressor 
off.
Cut-in - Temperature sensed by the 
controller that turns the compressor 
on.
REQUIRED TOOLS
•   Phillips Head Screwdriver
•   5/64” or 2 mm Allen Wrench
•   T-7 Torx Wrench
   __________  STEP  1  ___________
Unplug the cooler.
   __________  STEP  2  ___________
Remove the screws that secure the 
temperature control to the inset box 
lower left side of the cabinet (when 
facing the front of the cabinet).
   __________  STEP  3  ___________
Pull out gently from cabinet.
   __________  STEP  4  ___________
For high elevation installations, it 
may be necessary to “warm-up” the 
set points.  To make the adjustment, 
insert the appropriate tool in each 
adjustment screw and turn
1/4 of a revolution clockwise (to the 
right).  This procedure will adjust 
both the cut-in and cut-out about 2°F 
warmer.
   __________  STEP  5  ___________
Make sure to reconnect the pink wire 
to the proper spade terminal when 
reinstalling.
NOTE:
Mechanical temperature 
controllers are affected when 
functioning at high altitude.  
The cut-in and cut-out 
temperatures will be colder than 
when the controller functions 
closer to sea level
Danfoss Temperature Control (High Altitude Only!)
Cut-out Adjustment Screw Allen (5/64” 
or 2 mm) (clockwise for warmer)
Cut-in Adjustment Screw Torx (T-7)
(clockwise for warmer)
Compressor Connection(pink)
Compressor Connection
(pink)