Reliance Water Heaters HE50 76N Series 100 用户手册

下载
页码 40
16
therMal eXpansIon
As water is heated, it expands (thermal expansion). In a closed system
the volume of water will grow when it is heated. As the volume of water 
grows there will be a corresponding increase in water pressure due 
to thermal expansion. Thermal expansion can cause premature tank 
failure (leakage). This type of failure is not covered under the limited
warranty. Thermal expansion can also cause intermittent Temperature-
Pressure Relief Valve operation: water discharged from valve due to 
excessive pressure build up. This condition is not covered under the 
limited warranty. The Temperature-Pressure Relief Valve is not intended 
for constant relief of thermal expansion.
A properly sized thermal expansion tank must be installed on all closed 
systems to control the harmful effects of thermal expansion. Contact a local 
plumbing service agency to have a thermal expansion tank installed.
note: to protect against untimely corrosion of hot and cold 
water fittings, it is strongly recommended that di-electric unions 
or couplings be installed on this water heater when connected 
to copper pipe.
All gas piping must comply with local codes and ordinances or with 
the National Fuel Gas Code (ANSI Z223.1/ NFPA-54) or the Natural
Gas and Propane Installation Code (CAN/CSA B149.1) whichever
applies. Copper and brass tubing and fittings (except tin lined copper
tubing) should not be used.
fIGure 10.
Figure 10 shows typical attachment of water piping to the water heater. 
The water heater is equipped with 3/4 inch NPT water connections.
note: If using copper tubing, solder tubing to an adapter before 
attaching the adapter to the water heater connections.  do not 
solder the water lines directly to the water heater connections.  
It will harm the dip tube and damage the tank.
T & P Valve and Pipe Insulation (if supplied)
Remove insulation for T & P valve and pipe connections from carton.
fIGure 11.
Fit pipe insulation over the incoming cold water line and the hot water 
line. Make sure that the insulation is against the top cover of the heater.
Fit T & P valve insulation over valve. Make sure that the insulation 
does not interfere with the lever of the T & P valve.
Secure all insulation using tape.
teMperature-pressure relIef valve
Explosion Hazard
Temperature-Pressure Relief Valve
must  comply  with  ANSI Z21.22-
CSA 4.4 and ASME code.
Properly sized Temperature-Pressure 
Relief Valve must be installed in 
opening provided.
Can  result  in  overheating  and
excessive  tank  pressure.
Can cause serious injury or death.
This water heater is provided with a properly rated/sized and certified
combination Temperature-Pressure Relief Valve (T&P valve) by the
manufacturer. The valve is certified by a nationally recognized testing
laboratory that maintains periodic inspection of production of listed 
equipment of materials as meeting the requirements for Relief Valves 
for Hot Water Supply Systems, ANSI Z21.22 • CSA 4.4, and the code
requirements of ASME.
If replaced, the new T&P valve must meet the requirements of local 
codes, but not less than a combination Temperature-Pressure Relief 
Valve rated/sized and certified as indicated in the above paragraph.
The new valve must be marked with a maximum set pressure not to 
exceed the marked hydrostatic working pressure of the water heater 
(150 psi = 1,035 kPa) and a discharge capacity not less than the
water heater Btu/hr or kW input rate as shown on the water heater’s
model rating plate.
Note: In addition to the factory installed Temperature-Pressure Relief 
Valve on the water heater, each remote storage tank that may be installed 
and piped to a water heating appliance must also have its own properly 
sized, rated and approved Temperature-Pressure Relief Valve installed. 
Call the toll free technical support phone number listed on the back cover 
of this manual for technical assistance in sizing a Temperature-Pressure 
Relief Valve for remote storage tanks.
For safe operation of the water heater, the Temperature-Pressure 
Relief Valve must not be removed from its designated opening nor 
plugged. The Temperature-Pressure Relief Valve must be installed 
directly into the fitting of the water heater designed for the relief
valve. Install discharge piping so that any discharge will exit the 
pipe  within  6  inches  (15.2  cm)  above  an  adequate  floor  drain,
or external to the building. In cold climates it is recommended 
that it be terminated at an adequate drain inside the building. Be 
certain that no contact is made with any live electrical part. The