Roberts Gorden Caribe CGTH-30 用户手册

下载
页码 58
SECTION 9: T
ROUBLESHOOTING
  
37
Pressure switch does not 
Check flue/air supply duct for obstructions; remove any obstructions.
operate.
Check for loose/leaky air hoses to the pressure switch; repair/
replace/tighten hoses as required. Check for 24V across the secondary 
terminals 4 and 5 (red and yellow wires) of the transformer. 
IF NO: Check for 120V across the primary terminals 1 and 3 (black and 
white wires) of the transformer. If 120V is present, replace 
transformer. If 120V is not present, check wiring between power 
cord, blower motor and transformer.
IF YES:Connect a jumper wire across pressure switch terminals; if jumper 
wire allows blower to operate, replace pressure switch
(See Page 45, Section 12.1.1 for part number that applies to your 
unit rating). Do not resume normal heater operation until
replacement pressure switch has been installed.
Igniter spark gap incorrect.
Reset spark gap to 1/8" (3.175 mm).
BURNER DOES NOT LIGHT
Possible Cause
Try this....
Air in the gas line.
Purge gas lines.
Improper gas inlet pressure.
Check gas inlet pressure at the supply line. Gas inlet pressure should be 
as follows:
Natural Gas:
5.0" w.c. (12.4 mbar) minimum; 
14.0" w.c. (34.8 mbar) maximum
LP Gas:
11.0" w.c. (27.4 mbar) minimum; 
14.0" w.c. (34.8 mbar) maximum
If gas inlet pressure does not meet inlet pressure requirements, contact 
the gas company.
Gas valve does not open.
Check for 24V across valve terminals.
IF NO: Check wiring between the ignition module and the valve. Repair/
replace wires as required. If wiring is OK, replace ignition module.
IF YES:  Replace gas valve.
Low gas outlet pressure.
Check gas manifold pressure. Measure manifold pressure at the pressure 
tap on the gas valve. See Page 35, Figure 33 and Page 38, Figure 34.
Natural Gas:
3.5" w.c. (8.7 mbar)
LP Gas:
10.5" w.c. (26.1 mbar)
If manifold pressure does not meet requirements, adjust valve outlet 
pressure with the adjustment screw on the valve.
NOTE: Proper inlet gas pressure must be verified before performing outlet 
pressure testing.
Get user manuals: 