Reliance Water Heaters 317686-000 用户手册

下载
页码 40
16
discharge opening must not be blocked or reduced in size under any 
circumstances. Excessive length, over 30 feet (9.14 m), or use of
more than four elbows can cause restriction and reduce the discharge 
capacity of the valve.
No  valve  or  other  obstruction  is  to  be  placed  between  the 
Temperature-Pressure  Relief  Valve  and  the  tank.  Do  not  connect 
discharge piping directly to the drain unless a 6” (15.2 cm) air gap is
provided. To prevent bodily injury, hazard to life, or property damage, 
the  relief  valve  must  be  allowed  to  discharge  water  in  adequate 
quantities  should  circumstances  demand.  If  the  discharge  pipe  is 
not  connected  to  a  drain  or  other  suitable  means,  the  water  flow
may cause property damage.
CAUTION
• 
Temperature-Pressure Relief Valve discharge
  pipe must terminate at adequate drain.
Water Damage Hazard
t&p valve discharge pipe requirements:
•  Should not be smaller in size than the outlet pipe size of the valve, or 
  have any reducing couplings or other restrictions.
•  Should not be plugged or blocked.
•  Should not be exposed to freezing temperatures.
•  Should be of material listed for hot water distribution.
•  Should be installed so as to allow complete drainage of both the 
  Temperature-Pressure Relief Valve and the discharge pipe.
•  Must terminate a maximum of six inches above a floor drain or external 
  to the building. In cold climates, it is recommended that the discharge 
  pipe be terminated at an adequate drain inside the building.
•  Should not have any valve or other obstruction between the relief 
  valve and the drain.
DANGER
• 
Burn hazard.
• 
Hot water discharge.
• 
Keep clear of Temperature-
  Pressure Relief Valve
  discharge outlet.
The Temperature-Pressure Relief Valve must be manually operated at 
least twice a year. Caution should be taken to ensure that (1) no one
is in front of or around the outlet of the Temperature-Pressure Relief 
Valve discharge line, and (2) the water manually discharged will not
cause any bodily injury or property damage because the water may be 
extremely hot. If after manually operating the valve, it fails to completely 
reset and continues to release water, immediately close the cold water 
inlet to the water heater, follow the draining instructions in this manual, 
and replace the Temperature-Pressure Relief Valve with a properly 
rated/sized new one.
note: The purpose of a Temperature-Pressure Relief Valve is to 
prevent excessive temperatures and pressures in the storage tank. 
The T&P  valve  is  not  intended  for  the  constant  relief  of  thermal 
expansion. A properly sized thermal expansion tank must be installed 
on all closed systems to control thermal expansion, see Closed Water 
Systems and Thermal Expansion on page 14 and 15.
If you do not understand these instructions or have any questions 
regarding  the  Temperature-Pressure  Relief  Valve  call  the 
toll  free  number  listed  on  the  back  cover  of  this  manual  for  
technical assistance.
hIGh altItude InstallatIon
This heater is approved for operation up to 5,300 feet (1,615 m)
without alteration. High altitude models are available from the factory 
for elevations between 5,300 feet (1,615 m) and 10,100 feet (3,079
m).  For  elevations  above  10,100  feet  (3,079  m)  the  input  rating
should be reduced at the rate of 4 percent for each 1,000 feet (305
m) above sea level which requires replacement of the burner orifice
in accordance with National Fuel Gas Code (ANSI Z223.1/NFPA 54).
Contact your local gas supplier for further information.
Failure to replace standard orifice with a high altitude orifice when
installed above 10,100 feet (3,079 m) could result in improper and
inefficient operation of the appliance, producing carbon monoxide
gas in excess of safe limits, which could result in serious injury or 
death. Contact your gas supplier for any specific changes which
may be required in your area. 
Gas pIpInG
Fire and Explosion Hazard
Do  not  use  water heater with any
gas other than the gas shown on
the rating plate.
Excessive  pressure to gas control
valve can cause serious injury or death
Turn off gas lines during installation.
Contact qualified installer or 
service agency.
Make sure the gas supplied is the same type listed on the model 
rating plate. The inlet gas pressure must not exceed 14 inch  water 
column (3.5 kPa) for natural and propane gas (L.P.). The minimum
inlet gas pressure shown on the rating plate is that which will permit 
firing at rated input.
All gas piping must comply with local codes and ordinances or with the 
National Fuel Gas Code (ANSI Z223.1/ NFPA-54). Copper or brass
tubing and fittings (except tin lined copper tubing) should not be
used.
If the gas control valve is subjected to pressures exceeding 1/2 psi 
(3.5 kPa), the damage to the gas control valve could result in a fire
or explosion from leaking gas.
If  the  main  gas  line  Shuttoff  serving  all  gas  appliances  is  
used,  also  turn  “off”  the  gas  at  each  appliance.  Leave  all
gas  appliances  shut  “off”  until  the  water  heater  installation  
is complete.