Eaton 9SX11Ki 9SX11KI 产品宣传页

产品代码
9SX11KI
下载
页码 2
In the interests of continuous product improvement all specifications are subject to change without notice. 
© 2013 Eaton Corporation, All Rights Reserved, Eaton 9SX datasheet Rev B, January 2013.
Eaton 9SX UPS
Technical Specifications
5kVA
6kVA
8kVA
11kVA
Rating (kVA/kW)
5kVA/4.5kW
6kVA/5.4kW
8kVA/7.2kW
11kVA/10kW
Electrical Characteristics
Technology
On-line double conversion with Power Factor Correction (PFC) system
Nominal voltage
200/208/220/230/240V
200/208/220/230/240V/250V
Input voltage range
176-276V without derating (up to 100–276V with derating)
Output voltage/THDU
200/208/220/230/240V +/– 1%; THDU <2%
200/208/220/230/240/250V +/– 1%; THDU <2%
Input frequency range/THDI
40-70Hz, 50/60Hz autoselection, frequency converter as standard, THDI < 5%
Efficiency
Up to 94% in Online mode, 98% in Hi-Efficiency mode
Up to 95% in Online mode, 98% in Hi-Efficiency mode
Crest factor/short circuit current
3:1/90A
3:1/90A
3:1/120A
3:1/150A
Overload capacity
102–110% : 120s, 110–125%: 60s, 125–150%: 10s, >150%: 500ms
102–110% : 120s, 110–125%: 60s, 125–150%: 10s, >150%: 900ms
Connections
Input
Terminal block (up to 10 mm
2
)
Terminal block (up to 16mm
2
)
Outputs
Terminal block + 2 controlled groups of 4 IEC C13 (10A) + 2 IEC C19 (16A)
Terminal block
Batteries
Typical backup times at 50 and 70% load*
9SX
13/10 min
11/8 min
15/10 min
9/5min
9SX + 1 EBM
60/40 min
48/34 min
38/25 min
22/15 min
9SX + 4 EBM
220/150 min
170/120 min
120/82 min
80/55 min
Battery management
ABM
®
 and Temperature compensated charging method (user selectable), automatic battery test, deep discharge protection, automatic  
recognition of external battery units.
Communication
Communication ports
1 USB port, 1 RS232 serial port (USB and RS232 ports cannot be used simultaneously), 4 dry contacts (DB9), 1 mini terminal block for remote On/
Off and 1 for remote power Off.
Communication slot
1 slot for Network-MS card, ModBus-MS or Relay-MS cards.
Operating conditions, standards and approvals
Operating temperature
0 to 40°C continuous
Noise level
<45dB 
<45dB 
<48db
<50db
Safety
IEC/EN 62040-1, UL 1778, CSA 22.2
EMC, performance
IEC/EN 62040 -2 , FCC Class A, IEC/EN 62040-3 (Performance)
Approvals
CE, CB report (TUV), UL
Dimensions H x W x D/Weight
UPS
440(19’’)*130(3U)*685mm/48kg
440(19’’)*130(3U)*685mm/48kg
440(19’’)*260(6U)*700mm/84kg
440(19’’)*260(6U)*700mm/86kg
EBM
440(19’’)*130(3U)*645mm/68kg
440(19’’)*130(3U)*645mm/68kg
440(19’’)*130(3U)*680mm/65kg
440(19’’)*130(3U)*680mm/65kg
Power module
440(19’’)*130(3U)*700mm/19kg
440(19’’)*130(3U)*700mm/21kg
Customer Service and Support
Warranty
2 years warranty
* Runtimes are shown at 0.7 power factor. Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc
Parts Numbers
9SX 5kVA
9SX 6kVA 
9SX 8kVA
9SX 11kVA
UPS 
9SX8Ki
9SX11Ki
UPS with Rack Kit
9SX5KiRT
9SX6KiRT
9SX8KiRT
9SX11KiRT
EBM
9SXEBM240
9SXEBM240
EBM with Rack Kit
9SXEBM180RT
9SXEBM180RT
Power Module
9SX8KiPM
9SX11KiPM
HotSwap Maintenance ByPass
MBP6Ki
MBP6Ki
MBP11Ki
MBP11Ki
Transformer Module
TFMR11Ki
TFMR11Ki
TFMR11Ki
TFMR11Ki
Supercharger with Rack Kit
SC240RT
SC240RT
1.8m Battery Connection Cable
EBMCBL180
EBMCBL180
EBMCBL240
EBMCBL240
Battery Integration System
BINTSYS
BINTSYS
BINTSYS
BINTSYS
Rack Kit
9RK
9RK
9RK
9RK
1  Remote Off/On and Remote 
Power Off connectors
2  Slot for Network-MS,  
ModBus-MS or Relay-MS cards 
3  External battery module 
(EBM) connector with 
automatic detection (RJ11)
4  DB 9 with output contacts
5  USB and serial ports
6  Input/Ouput connections
Eaton 9SX 11kVA