12. Operation 
Control 
12.1 Basic Function 
12.1.1  Internal Setting Temperature 
Once the operation starts, remote control setting temperature will be taken as base value for temperature shifting 
processes. These shifting processes are depending on the air conditioner settings and the operation environment. 
The final shifted value will be used as internal setting temperature and it is updated continuously whenever the 
electrical power is supplied to the unit. 
12.1.2  Cooling Operation  
12.1.2.1 Thermostat 
control 
• Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -1.5
к
• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > 
Compressor OFF point. 
12.1.3  Soft Dry Operation 
12.1.3.1 
Thermostat control (The same as Cooling mode) 
12.1.4 Heating 
operation 
12.1.4.1 Thermostat 
control 
• Compressor is OFF when Intake Air Temperature - Internal Setting Temperature > +2.0
к
• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature< 
Compressor OFF point. 
12.1.5 Automatic 
Operation 
1. Once AUTO mode is selected, operation mode is   determined by set temperature of remote control, indoor 
intake temperature and outdoor temperature. 
2.During operating mode judgment, indoor fan runs at min Lo- fan speed and outdoor fan runs in the purpose of 
detecting the intake air temperature and outdoor air temperature (for 30 seconds) 
Remote Control Setting Temp. (16
к~30к)
Indoor Air Temperature Shifting
Outdoor Air Temperature Shifting
Internal Setting Temperature
Powerful Temperature Limit Checking ( Min:16
к; Mac:33к)
Internal Setting Temperature