Tuncmatik Newtech Pro Plus 6 kVA TSK3514 用户手册
产品代码
TSK3514
18
reserved
11: reserved
Interface
Setting
reserved
12: Hot standby function enable/disable
Interface
Setting
Parameter 2: HS.H
Enable or disable Hot standby function. You may choose following
two options in Parameter 3:
YES: Hot standby function is enabled. It means that the current
UPS is set to host of the hot standby function, and it will restart
after AC recovery even without battery connected.
NO: Hot standby function is disabled. The UPS is running at
normal mode and can’t restart without battery
13: Battery voltage calibration
Interface
Setting
Parameter 2: Select “Add” or “Sub” function to calibrate battery
voltage to real figure.
Parameter 3: the voltage range is from 0V to 5.7V, the default
value is 0V.
14: Charger voltage adjustment
Interface
Setting
Parameter 2: you may choose Add or Sub to adjust charger
voltage
Parameter 3: the voltage range is from 0V to 6.4V, the default
value is 0V.
15: reserved
Interface