页码 2
ENVIRONMENT
PROTECTION
SPECIFICATION
MODEL
RS-150-3.3
RS-150-5
RS-150-12
RS-150-15
RS-150-24
RS-150-48
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max.)
Note.2
OUTPUT
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
Note.3
LINE REGULATION
Note.4
LOAD REGULATION
Note.5
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY(Typ.)
AC CURRENT (Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
SAFETY STANDARDS
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSION
OTHERS
NOTE
PACKING
OVERLOAD
Note.8
OVER VOLTAGE
3.3V
5V
12V
15V
24V
48V
30A
26A
12.5A
10A
6.5A
3.3A
0 ~ 30A
0 ~ 26A
0 ~ 12.5A
0 ~ 10A
0 ~ 6.5A
0 ~ 3.3A
99W
130W
150W
150W
156W
158.4W
80mVp-p
80mVp-p
120mVp-p
120mVp-p
120mVp-p
200mVp-p
3.2V ~ 3.5V
4.75 ~ 5.5V
11.4 ~ 13.2V
14.25 ~ 16.5V
22.8 ~ 26.4V
45.6 ~ 52.8V
3.0%
2.0%
1.0%
1.0%
1.0%
1.0%
0.5%
0.5%
0.5%
0.5%
0.5%
0.5%
2.0%
1.0%
0.5%
0.5%
0.5%
0.5%
800ms, 20ms/230VAC
1200ms, 30ms/115VAC at full load
28ms/230VAC
20ms/115VAC at full load
88 ~ 132VAC / 176 ~ 264VAC selected by switch
248 ~ 373VDC(Withstand 300VAC surge for 5sec. Without damage)
47 ~ 63Hz
74%
3.8 ~ 4.45V
5.75 ~ 6.75V
13.8 ~ 16.2V
17.25 ~ 20.25V
27.6 ~ 32.4V
55.2 ~ 64.8V
78%
83%
84%
86%
87%
3A/115VAC
2A/230VAC
COLD START 40A/230VAC
<2mA / 240VAC
110 ~ 150% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
UL60950-1, TUV EN60950-1 approved
Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
-25 ~ +70
(Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +85
, 10 ~ 95% RH
0.03%/
(0 ~ 50
)
10 ~ 500Hz, 5G 10min./1cycle, period for 60min. each along X, Y, Z axes
244KHrs min.
MIL-HDBK-217F (25
)
199*98*38mm (L*W*H)
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25
of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Line regulation is measured from low line to high line at rated load.
5. Load regulation is measured from 0% to 100% rated load.
6. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
7. Length of set up time is measured at cold first start. Turning ON/OFF the power supply very quickly may lead to increase of the set up time.
8. Extra consideration should be taken when selecting output wiring for 3.3V and 5V models. This is to prevent the protection modes for overload and short
circuit from becoming constant power.
For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
(as available on http://www.meanwell.com)
Protection type : Hiccup mode, recovers automatically after fault condition is removed
0.7Kg; 20pcs/15Kg/0.8CUFT
150W Single Output Switching Power Supply
R S - 1 5 0
s e r i e s
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC
I/P-FG:1.5KVAC
O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25
/ 70% RH
SAFETY &
EMC
(Note 6)
Protections: Short circuit / Overload / Over voltage
Cooling by free air convection
LED indicator for power on
100% full load burn-in test
All using 105
Withstand 300VAC surge input for 5 second
High operating temperature up to 70
Withstand 5G vibration test
High efficiency, long life and high reliability
3 years warranty
long life electrolytic capacitors
Features :
EMC IMMUNITY
EMC EMISSION
File Name:RS-150-SPEC 2011-08-19