Enda EI7412-SM-AS12 SW Universal LED-display EI7412 0 - 20 mA/4 - 20 mA/0 - 1 V/0 - 10 V Assembly dimensions 68 x 68 mm EI7412-SM-AS12 SW 数据表

产品代码
EI7412-SM-AS12 SW
下载
页码 4
Read this document carefully before using this device. The guarantee will be expired by 
damaging of  the device if you don't attend to the directions in the user manual. Also we don't 
accept any compensations for personal injury, material damage or capital disadvantages.  
Thank you for choosing ENDA EI7412 INDICATOR
TECHNICAL SPECIFICATIONS
HOUSING
 Housing type
 Suitable for flush-panel mounting according to DIN 43 700.
 Dimentions  
 W72xH72xD97mm 
 Weight 
 Approx. 350g (after packaging)
 Enclosure material
 Self extinguishing plastics.
 While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
ENDA EI7412 PROGRAMMABLE INDICATOR WITH RELAY  
 * 72x72mm sized.
 * 4 digits display.
 * On-offcontrol.
 * Relays for Out and Alarm control.
 * Up and low limits of Set values can be configured.
 * Decimal point can be adjusted between 1. and 3. digits.
 * Display scale can be adjusted between -1999 and 4000.
 * Measurement unit can be displayed.
 * Selectable four different standart input types (0-20mA, 4-20mA, 0-1V, 0-10V).
 * User can calibrate the device according to his/her own specified input type.
 * Sampling time can be adjusted in four steps.
 * Selectable control option below and above the set value.
 * Selectable independent, deviation or band alarms.
 * Maximum and minimum values are registered and can be hold on the display.
 * Current and voltage calibration can be made.
 * Selectable parameter access protection.
 * CE marked according to European Norms.
   Order code :  EI7412--
1               2
1 - Supply Voltage
     230VAC...230V AC
     24VAC.....24V AC 
     SM...........9-30V DC / 7-24V AC
2 - Auxilary Supply OUT
     AS24.....24V DC 50mA
     AS12.....12V DC 50mA
     AS08.....8V DC 50mA
     AS05.....5V DC 50mA
     None.......No auxilary supply out
OUTPUTS
 Auxilary power supply 
 All auxilary power supplies supply maximum 50mA (Regulated and isolated)
 Out
 Relay: 250V AC, 8A (for resistive load), NO; 1/2 HP 240V AC CosF = 0.4 (for inductive load) 
 Alarm
 Relay: 250V AC, 8A (for resistive load), NO; 1/2 HP 240V AC CosF = 0.4 (for inductive load) 
 Life expectancy for relay
 Mechanical 30.000.000 operation; 100.000 operation at 250V AC, 8A resistive load.
CONTROL
 Control type
 Single set-point and alarm control
 Control algorithm
 On-Off control
 Hysteresis
 Adjustable between 1 ... 200 
ENVIRONMENTAL CONDITIONS
 Height
 Max. 2000m
 Ambient/storage temperature
 Max. relative humidity
0 ... +50°C/-25 ... +70°C  (with no icing)  
Rated pollution degree
80% up to 31°C decreasing linearly  50% at 40°C. 
According to EN 60529                Front panel :   IP65
                                                       Rear panel  :    IP20
 Do not use the device in locations subject to corrosive and flammable gases.
  EI7412  must not be used in location where measurement category is II, III or IV.
 Supply
230VAC +10%/-20%, 50/60Hz, 24VAC±10%,50/60Hz or 24Vac/dc (9-30Vdc or 7-24Vac)
 Power consumption
Max. 7VA
2.5mm² screw-terminal connections
 Wiring
 Date retention 
 EMC
 Safety requirements
 EN 61326-1: 1997, A1: 1998, A2: 2001 (Performance criterion B for the EMC standard)  
EEPROM (Min. 10 years)
 EN 61010-1: 2001 (pollution degree 2, overvoltage category II, measurement category I)
ELECTRICAL CHARACTERISTICS
In the current measurement mode input impedance is 5W. Therefore, in the current measurement mode, any voltage input 
should not be connected to the input terminals. Otherwise, the device will be broken down. To change the input type from 
voltage to a current measurement mode while the device is operating, first, leave out the voltage inputs. Then, change 
input type to one of the current measurement modes. 
Input type
 0-1V DC voltage
 0-10V DC voltage
 0-20mA DC current
 4-20mA DC current
 Input empedance
Approx. 11kW (terminal voltage limits:  min. =  -2V,  max. = 30V)
Approx. 11k
W (terminal voltage limits:  min. =  -2V,  max. = 30V) 
Approx. 5
W  (applicable terminal voltage is max. 50mA.)
Approx. 5
W  (applicable terminal voltage is max. 50mA.)
0V
±0,5% (of full scale) 
0V
±0,5% (of full scale)
0mA
±0,5% (of full scale)
0mA
±0,5% (of full scale)
 1.1V
 14V
 25mA
 25mA
 Min.
Max.
Measurement range Measurement accuracy
      PROGRAMMABLE INDICATOR
ENDA
EI 7412
OSET
SET
MAX             
ASET
OUT
ALR
MIN             
E-mail :   info@suran-elektronik.de
Internet : www.suran-elektronik.de
Tel.:  +49 (0)7451 / 625 617
Fax:  +49 (0)7451 / 625 0650
SURAN 
Industrieelektronik
Dettinger Str. 9 / D-72160 Horb a.N
1./4     EI7412-E
english
u
p
 t
o
 d
a
te
0
1
0
9
2
0
0
9
 m
o
d
if
ic
a
ti
o
n
  
re
s
e
rv
e
d
 a
n
d
 c
a
n
 b
e
 c
h
a
n
g
e
 a
n
y
 t
im
e
 p
re
v
io
u
s
 n
o
ti
c
e
 !