1. Description
SUBCON-PLUS-PROFIB plug with spring-cage connection or
screw-cage connection for axial cable entry.
screw-cage connection for axial cable entry.
The plug allows fast and convenient connection of incoming
and outgoing bus cables. Its contacts are routed onto clearly
color labeled spring-cage terminal blocks or screw-cage
terminal blocks.
and outgoing bus cables. Its contacts are routed onto clearly
color labeled spring-cage terminal blocks or screw-cage
terminal blocks.
The integrated terminal resistor can be connected and
simultaneously connects/disconnects the outgoing bus cable
when de/activating. This allows an easy start up of the bus
system one segment at a time.
simultaneously connects/disconnects the outgoing bus cable
when de/activating. This allows an easy start up of the bus
system one segment at a time.
Strain relief and shield bonding are integrated into the two
housing shells. Mount the upper shell of the housing to build up
strain relief and shield bonding for the bus cable.
housing shells. Mount the upper shell of the housing to build up
strain relief and shield bonding for the bus cable.
The strain relief is designed for FastConnect bus cables with an
overall cross section of 8 mm.
overall cross section of 8 mm.
2. Notes on Connecting
The following stripping tools can be used to strip conductors
quickly and conveniently (Fig.2):
PSM-STRIP-FC/PROFIB (Order No.: 27 44 62 3) and
QUICK-WIREFOX 6
quickly and conveniently (Fig.2):
PSM-STRIP-FC/PROFIB (Order No.: 27 44 62 3) and
QUICK-WIREFOX 6
(Order No.: 12 04 38 4).
2.1. Spring-Cage Connection
SUBCON-PLUS-PROFIB/AX
2.1.1. Stripping lengths
Please observe the
recommended
recommended
stripping
lengths
(Fig.3).
3
4
Fig.2
1
2
6
9
9
24 mm
Fig.3
2.1.2. Connection
Push the stripped conductor into
the corresponding contacts of
the terminal block. The
conductors automatically make
contact when inserted.
the corresponding contacts of
the terminal block. The
conductors automatically make
contact when inserted.
To disconnect the conductor, it is
necessary to implement the
orange disconnect rocker.
necessary to implement the
orange disconnect rocker.
2.2. Screw-Cage Connection
SUBCON-PLUS-PROFIB/AX/SC
2.2.1. Stripping lengths
Please observe the
recommended
recommended
stripping
lengths
(Fig.5).
2.2.2. Connection
Push the stripped conductor into
the corresponding contacts of
the terminal block.
the corresponding contacts of
the terminal block.
Fig.4
6
13
5
24 mm
Fig.5
2B
2
A
1
B
1
A
Fig.6
3. Bus Terminating Resistor
3.1. Activating terminating resistor and
switching off outgoing bus cables:
The terminating resistors are activated via the slide switch
(Fig.1) at the starting and final point of the bus system. At the
same time the connection points (2A/2B) for the outgoing bus
cable are switched off.
(Fig.1) at the starting and final point of the bus system. At the
same time the connection points (2A/2B) for the outgoing bus
cable are switched off.
At all other nodes of the bus system the corresponding
terminating resistor must be deactivated!
terminating resistor must be deactivated!
Bus Cable Connection
Always connect the incoming bus cable to the connection
points 1A/1B (also at the starting point of the bus system!).
points 1A/1B (also at the starting point of the bus system!).
The outgoing bus cable is always connected to the connection
points 2A/2B (see Fig.8).
points 2A/2B (see Fig.8).
≈
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
OFF
OFF
OFF
OFF
Start
End
Fig.7
4. Function Block Diagram
1A
8
OFF
S1
D(N)
390
Ω
220
Ω
390
Ω
1B
2A
2B
3
5
6
D(P)
GND
VP
ON
Fig.8
5. Technical Data
Type
/ Order No.
SUBCON-PLUS-PROFIB/AX
27 44 37 7
SUBCON-PLUS-PROFIB/AX/SC
27 44 38 0
Plug connection
9-pos. SUB-D male connector
Insertion/withdrawal
min. 200
Cable cross section
max. / min.
8 mm (± 0.4 mm)
Mounting screws /
max. torque
max. torque
4-40 UNC /
0.4 Nm
0.4 Nm
Housing material
ABS, metal-plated
Temperature range
-20°C to +75°C
Spring-cage
connection
connection
Connection cross section
• rigid
• AWG
• rigid
• AWG
0.12-0.5 mm
2
28-20
Screw-cage connection
Connection cross section
• rigid
• flexible
• AWG
• rigid
• flexible
• AWG
0.14-1.5 mm
2
0.14-1.0 mm
2
26-16
Bus cable
The plug is specified for cable type A
according to EN 50 170.
Cable type B, also described in EN 50 170,
is outdated and must not be used anymore.
according to EN 50 170.
Cable type B, also described in EN 50 170,
is outdated and must not be used anymore.
6. Dimensions
Linear extension acc. to the PROFIBUS specification
Transmission rate in kbit/s
corresponding
segment length in m
segment length in m
9.6 / 19.2 / 45.45 / 93.75
1,200 m
187.5
1,000 m
500
400 m
1,500
200 m
3,000 / 6,000 / 12,000
100 m
ON
OFF
17
20
31,5
58,2